1 |
|
| Notes |
| Date |
Text |
| 2010-10-01 10:57:45 | BUILDING PLAN REVIEW | | | PERMIT: 10080635 | | | ADD: 8085 IRONHORSE BLVD | | | CONT: GLOBE TEC CONSTRUCTION | | | | | | TEL: (954)214-3759 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLANS FAIL TO PROVIDE HOW THE GENERATOR WILL COMPLY | | | WITH FBC-B 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO | | | RESIST OVERTURNING EFFECTS CAUSED BY TTHE LATERAL | | | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR | | | WIND. SHEET E-5 NOTE 5. | | | | | | 2) SHEET E-5 INDICATES A DOUBLE WALL STEEL BASE TANK, | | | PLEASE PROVIDE MANUFACTURERS SPEC ON THIS TANK. | | | | | | BUILDING PLAN REVIEW | | | PERMIT: | | | ADD: | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | REVIEW | | | ACTION: DENIED |
|