| Plan Review Notes For Permit 10080630 |
| Permit Number |
10080630 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-07 12:01:51 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) PROVIDE HYDRAULIC CALCULATIONS. | | | | | | 2) PROVIDE CORRECT ORIFICE SIZE IN LEGEND FOR | | | SPRINKLERS WITH K-FACTOR LESS THAN 5.6. | | | | | | 3) TWO SIDEWALL SPRINKLERS NEAR BALCONY HAVE SPRAY | | | OBSTRUCTED BY SOFFITS. | | | | | | 4) LIGHT FIXTURE LOCATIONS NOT PROVIDED; HOWEVER, THE | | | MINIMUM DISTANCE BETWEEN LIGHT FIXTURES AND RESIDENTIAL | | | SIDEWALL SPRINKLERS IS 8'-0". VERIFY SPRAY IS NOT | | | OBSTRUCTED. | | | | | | 5) IS THE EXISTING BALCONY PROTECTED BY SPRINKLERS? | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|