Plan Review Notes
Plan Review Notes For Permit 10080630
Permit Number 10080630
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-09-07 12:01:51*****REVIEW COMMENTS - FIRE*****
  
 1) PROVIDE HYDRAULIC CALCULATIONS.
  
 2) PROVIDE CORRECT ORIFICE SIZE IN LEGEND FOR
 SPRINKLERS WITH K-FACTOR LESS THAN 5.6.
  
 3) TWO SIDEWALL SPRINKLERS NEAR BALCONY HAVE SPRAY
 OBSTRUCTED BY SOFFITS.
  
 4) LIGHT FIXTURE LOCATIONS NOT PROVIDED; HOWEVER, THE
 MINIMUM DISTANCE BETWEEN LIGHT FIXTURES AND RESIDENTIAL
 SIDEWALL SPRINKLERS IS 8'-0". VERIFY SPRAY IS NOT
 OBSTRUCTED.
  
 5) IS THE EXISTING BALCONY PROTECTED BY SPRINKLERS?
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730