| Plan Review Notes For Permit 10080606 |
| Permit Number |
10080606 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-01 09:32:44 | FBC PLUMBING 2007 | | | REVIEW # 1 | | | DENIED: | | | | | | FBC PLUMBING 2007 403.1 MINIMUN FIXTURES - A-3 | | | OCCUPANCY REQUIRES SEPERATE FACILITIES FOR MEN AND | | | WOMEN | | | 1. MENS ADA RESTROOM - 1 WC PER 150, 1 LAVITORY PER 200 | | | 2. WOMENS ADA RESTROOM - 1 WC PER 75 , 1 LAVITORY PER | | | 200 | | | 3. 1 DRINKING FOUNTAIN IS REQUIRED PER 1,000 PERSONS. | | | 4. 1 SERVICE SINK IS REQUIRED. | | | | | | FBC PLUMBING 2007 607.1 HOT WATER IS REQUIRED FOR | | | SERVICE SINKS. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|