| 2010-10-29 10:10:45 | PALM BEACH COUNTY HOMELESS RESOURCE CENTER |
| | 1000-45TH STREET |
| | PERMIT NUMBER 10080589 |
| | |
| | |
| | 1. BUILDING ADDRESSES ARE REQUIRED TO BE POSTED ON THE |
| | BUILDINGS. THE BUILDING ADDRESS ONLY ON THE MARQUEE |
| | SIGN DOES NOT MEET CODE REQUIREMENTS. BUILDING |
| | ADDRESSES SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT |
| | LEAST 1" WIDE THAT CONTRAST TO THE BACKGROUND THAT THEY |
| | ARE AFFIXED TO. |
| | |
| | 2. ENSURE THAT EMERGENCY LIGHTS EXIST IN STAIRWELL |
| | 3-125 AND 3-128. |
| | |
| | 3. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE FLORIDA BUILDING CODE |
| | AND THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 4. ENSURE PANIC HARDWARE IS PRESENT ON EXIT DOORS IN |
| | DINING AREA IF OCCUPANT LOADS ARE EXPECTED TO 100 OR |
| | MORE PERSONS. |
| | |
| | 5. THE CHILDREN'S WAITING AREA SHALL BE EQUIPPED WITH |
| | DUPLEX OUTLETS PROTECTIVE COVERS. |
| | |
| | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 7. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A THIRD |
| | PARTY APPROVED FOR CENTRAL STATION SERVICE |
| | REQUIREMENTS. |
| | |
| | 8. ELECTRONIC LOCKING DEVICES USED ON EXIT DOORS SHALL |
| | COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE PREVENTION |
| | CODE (101 THE LIFE SAFETY CODE, 2006 EDITION) |
| | |
| | 9. SUBJECT TO FIELD INSPECTION AND APPROVAL. |
| | |
| | |
| | |
| | APPROVED PROVISO |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |