| 2010-08-30 15:35:49 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | PLAN REVIEW COMMENTS: |
| | |
| | 1. PG M-6 PLAN NOTE #1 CALLS FOR DRYER BOOSTER FAN. |
| | PROVIDE DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS |
| | SHOWING THE USE OF A BOOSTER FAN IS APPROVED BY THE |
| | DRYER MANUFACTURER. CLOTHES DRYERS SHALL BE EXHAUSTED |
| | IN ACCORDANCE WITH THE DRYER MANUFACTURER'S |
| | INSTRUCTIONS PER FBC-M 504.1. |
| | |
| | 2. PG M-6 AND M-7 PLAN NOTES 2 AND/OR 3 CALL FOR |
| | OUTSIDE AIR INTAKE LOUVERS. PROVIDE FULL PRODUCT |
| | APPROVAL DOCUMENTATION WITH INSTALLATION INSTRUCTIONS |
| | FOR LOUVERS IN ACCORDANCE WITH FBC-B 106.3.3 AND FBC-M |
| | 304.1. |
| | |
| | 3. PG M-6 BUILDINGS 1 AND 2: EXHAUST AIR FROM SOME FANS |
| | AND CLOTHES DRYERS ARE SHOWN DISCHARGING DIRECTLY OVER |
| | SIDEWALKS (SEE DRAWING MARK-UPS). EXHAUST AIR SHALL NOT |
| | BE DIRECTED ONTO WALKWAYS PER FBC-M 401.4.2. |
| | |
| | 4. PG M-7 PLAN NOTE #8 ON FIRST FLOOR AND PLAN NOTE #6 |
| | ON SECOND FLOOR CALL FOR DRYER BOOSTER FAN. PROVIDE |
| | DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS SHOWING |
| | THE USE OF A BOOSTER FAN IS APPROVED BY THE DRYER |
| | MANUFACTURER. CLOTHES DRYERS SHALL BE EXHAUSTED IN |
| | ACCORDANCE WITH THE DRYER MANUFACTURER'S INSTRUCTIONS |
| | PER FBC-M 504.1. |
| | |
| | 5. PG M-13: DETAIL #8 CALLS FOR RUSKIN IBD2 FIRE DAMPER |
| | AT RATED SUB-CEILING. BASED ON MANUFACTURER'S |
| | INSTRUCTIONS, THIS DAMPER IS NOT COMPATIBLE WITH THE |
| | SINGLE-MEMBRANE CEILING ASSEMBLY SHOWN ON PLANS. FIRE |
| | DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR |
| | LISTING AND MANUFACTURER'S INSTRUCTIONS PER FBC-M |
| | 607.2. |
| | |
| | 6. PG M-13 DETAIL #8 NOTE: FLEXIBLE DUCT CONNECTIONS |
| | ARE REQUIRED TO BE SEALED AND MECHANICALLY FASTENED. |
| | THEY ARE NOT INTENDED FOR REMOVAL AND USE FOR FIRE |
| | DAMPER ACCESS. PROVIDE RIGID DUCT WITH DUCT ACCESS |
| | DOOR. A SERVICE OPENING SHALL BE PROVIDED IN AIR DUCTS |
| | ADJACENT TO EACH FIRE DAMPER PER NFPA 90A SECTION |
| | 4.3.4.1. |
| | |
| | 7. ON ALL FLOOR PLANS: ADDITIONAL RATED SEPARATIONS ARE |
| | LIKELY AROUND SLEEPING ROOMS AND POSSIBLY EGRESS |
| | CORRIDORS (SEE BUILDING REVIEW COMMENTS). VERIFY THAT |
| | ALL PENETRATIONS OF ADDITIONAL RATED ASSEMBLIES ARE |
| | PROTECTES IN ACCORDANCE WITH FBC-M 607.5. |
| | |
| | 8. PG M-7: FLOOR PLAN SHOWS RETURN AIR GRILL IN LANDING |
| | KITCHEN 3-117. RETURN AIR INTAKE IS PROHIBITED IN |
| | NON-DEDICATED KITCHEN HVAC SYSTEMS PER FBC-M 407.1. |
| | |
| | 9. PG M-7 FIRST FLOOR PLAN NOTE #5 CALLS FOR FLY FAN AT |
| | EXTERIOR DOOR FOR LANDING KITCHEN 3-117. THIS FAN IS |
| | NOT IDENTIFIED ON PLANS TO CORRELATE WITH FAN SCHEDULE. |
| | PROVIDE MISSING INFORMATION PER FBC-B 106.1.1. |
| | |
| | 10. PG M-8 THRU M-11: PLAN NOTE #6 CALLS FOR CONDENSATE |
| | TO DISCHARGE INTO HUB DRAIN. CONDENSATE SHALL NOT |
| | DISCHARGE INTO SANITARY SEWER PER CITY ORDINANCE AND |
| | FBC-M 307.2.1. |
| | |
| | 11. PG M-8 THRU M-11: PLAN NOTE #4 CALLS FOR SMOKE |
| | DETECTOR TO BE PROVIDED IN SUPPLY AND RETURN DUCTS. |
| | PLAN AND SECTION VIEWS SHOW SMOKE DETECTORS ONLY IN THE |
| | SUPPLY DUCT. PLEASE COORDINATE PLANS, SECTIONS AND |
| | NOTES TO SHOW THE LOCATION OF ALL DUCT SMOKE DETECTORS |
| | PER FBC-M 106.1.1. |
| | |
| | 12. PG M-8 THRU M-11: DUCT ACCESS DOOR REQUIRED AT |
| | SMOKE DETECTORS PER FBC-M 301.15 AND NFPA 90A SECTION |
| | 4.3.4.1. |
| | |
| | 13. PG M-14 DETAIL #7: FIRE DAMPERS SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATIONS AND |
| | LISTING PER FBC-M 607.2. PROVIDE MANUFACTURER'S |
| | INSTRUCTIONS IN THE FIELD AND REMOVE ANY CONFLICTIONG |
| | INFORMATION FROM PLANS. |
| | |
| | 14. PG M-17 THRU M-19: SEQUENCE FOR FIRE/SMOKE CONTROL |
| | CALL FOF FAN TO BE SHUT DOWN BY DUCT SMOKE DETECTORS |
| | ONLY WHILE NOTE #4 ON PAGES M-8 THRU M-11 CALLS FOR |
| | FANS TO SHUT-DOWN UPON ACTIVATION OF ANY FIRE ALARM |
| | STATION. PLEASE COORDINATE AND CLARIFY PER FBC-B |
| | 106.1.1. |
| | |
| | 15. NO ENERGY CODE COMPLIANCE FORM OR COOLING LOAD |
| | CALCULATIONS PROVIDED FOR REVIEW. FBC-B CHAPTER 13. |
| | |
| | 16. NO INFORMATION PROVIDED REGARDING KITCHEN EXHAUST |
| | AND VENTILATION SYSTEMS. PROVIDE SEPARATE PLANS AND |
| | PERMIT APPLICATION FOR THESE SYSTEMS. |
| | |
| | PLEASE RESPOND TO EACH COMMENT IN WRITING, INDICIATING |
| | HOW EACH COMMENT HAS BEEN ADDRESSED AND WHERE THE |
| | REQUIRED INFORMATION CAN BE FOUND. RESPONSE LETTER MAY |
| | BE UPLOADED TO THE "SUPPORTING DOCUMENTS" FOLDER UPON |
| | RESUBMISSION OF CORRECTED PLANS. |
| | |