| Date |
Text |
| 2010-09-23 10:10:48 | 1000 45TH STREET |
| | HOMELESS SHELTER |
| | PERMIT #10080589 |
| | |
| | SHEET LSP-2: |
| | |
| | -PROVIDE VISUAL FIRE ALARM NOTIFICATION APPLIANCES IN |
| | ALL RESTROOMS. |
| | |
| | -PROVIDE ADDITIONAL INFORMATION ON DETEX DOOR HARDWARE. |
| | |
| | -SINGLE STATION SMOKE ALARMS ARE REQUIRED IN EVERY |
| | GUEST ROOM, LIVING AREA AND SLEEPING ROOM WITHIN A |
| | GUEST SUITE PER 28.3.4.5 (FFPC). |
| | |
| | -BUILDING #3: TRAVEL DISTANCE WITHIN A GUEST SUITE TO A |
| | CORRIDOR SHALL NOT EXCEED 75 FEET IN BUILDINGS |
| | PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM PER 28.2.6.2 |
| | (FFPC). |
| | |
| | -PERMANENTLY LOCKED DOORS SHALL BE LABELED WITH ???NO |
| | EXIT??? SIGNS. |
| | |
| | WESLEY JOLIN |
| | CITY OF WEST PALM BEACH |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | 561-805-6730 |
| | |
| | |
| 2010-09-13 12:04:39 | HOMELESS RESOURCE CENTER |
| | PERMIT NUMBER 10080589 |
| | 1000 BLOCK OF 45TH STREET |
| | |
| | 1. THE BUILDINGS PRIOR TO THE SUBMITTAL OF THESE PLANS |
| | WERE BEING USED AS A GROUP "B" OR BUSINESS USE. THE |
| | PROPOSED BUILDINGS AND DESIGNS ARE DIFFERENT FROM |
| | PREVIOUSLY USES WHICH SEEMS TO SUGGEST A CHANGE OF USE |
| | OF SOME OF THESE FACILITIES. |
| | |
| | 2. KNOX-BOXES WILL BE NEEDED FOR THE BUILDINGS. PLEASE |
| | GO TO WWW.KNOXBOX.COM TO ORDER THE BOXES. |
| | |
| | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS |
| | OFTEN AS NECESSARY. |
| | |
| | 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | |
| | 5. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 6. SMOKE DETECTION EQUIPMENT SHALL BE INSTALLED A |
| | MINIMUM OF AT LEAST THREE FEET FROM AIR CONDITIONER |
| | DIFFUSERS. |
| | |
| | 7. ELEVATOR WARNING SIGNS ARE NEEDED. |
| | |
| | 8. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| | AND FIRE SPRINKLER INSTALLATIONS. |
| | |
| | 9. AN EMERGENCY PLAN IS TO BE SUBMITTED TO THIS OFFICE. |
| | THIS EMERGENCY PLAN SHALL BE DEVELOPED USING AN "ALL |
| | HAZARDS" APPROACH AND SHOULD INCLUDE PLANNING AND |
| | TRAINING FOR FIRES, INCLEMENT WEATHER, MEDICAL |
| | EMERGENCIES, ETC. |
| | |
| | 10. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING |
| | FROM THE BUILDINGS. |
| | |
| | 11. ON PAGE E-4 AN ADDITIONAL EXIT SIGN APPEARS TO BE |
| | NEEDED ON THE OUTSIDE OF THE ADULT INTAKE AREA 1-136. |
| | |
| | 12. ON PAGE E-7 NO ILLUMINATED EXIT SIGNS OR EMERGENCY |
| | LIGHTING SHOWN FOR THE BUSINESS AREA. |
| | |
| | 13. ON SHEET LSP-1 DOORS "THAT ARE TO REMAIN LOCKED AT |
| | ALL TIMES" ARE PROVIDED WITH EGRESS CAPACITIES BUT ARE |
| | NOT EQUIPPED WITH EXIT SIGNS. IF THEY ARE NOT REQUIRED |
| | EXITS, THEN EGRESS CAPACITIES SHOULD NOT BE CALLED OUT. |
| | |
| | 14. AN EGRESS DOOR APPEARS TO BE IN CLOSE PROXIMITY TO |
| | AN UNPROTECTED WINDOW OPENING FROM AN ADJACENT BUILDING |
| | ON PAGE LSP-1. |
| | |
| | 15. PLEASE INDICATE THE COMBUSTIBILITY FACTOR FOR THE |
| | PROPOSED MATTRESSES. |
| | |
| | 16. ALL RATED FIRE DOORS ARE TO BE PROPERLY LABELED AND |
| | BE EQUIPPED WITH SELF-CLOSING DEVICES TO CAUSE THE |
| | DOORS TO POSITIVELY LATCH WHEN OPENED. |
| | |
| | 17. PLEASE INDICATE THE LOCATIONS OF "NO SMOKING" SIGNS |
| | AND AREAS AND THE LOCATIONS OF DESIGNATED SMOKING AREAS |
| | AND SIGNAGE. |
| | |
| | 18. PLEASE EXPLAIN THE TERM "LANDING KITCHEN" AS |
| | ILLUSTRATED ON THE PLANS. |
| | |
| | 19. GAS SERVICES SHALL COMPLY WITH NFPA 54, 2006 |
| | EDITION. |
| | |
| | 20. PLEASE INDICATE CONTENTS AND AMOUNT OF MATERIALS IN |
| | THE BUFFER TANK ON SHEET M-12. |
| | |
| | 21. ON LSP-1 "FAMILY ROOMS" ARE NOTED. PLEASE INDICATE |
| | PURPOSE AND FURNISHINGS PLANNED FOR THESE ROOMS. ARE |
| | ANY SLEEPING PURPOSES PLANNED FOR THESE ROOMS. |
| | |
| | 22. FAMILY ROOM # 3 HAS TRAVEL DISTANCE GOING THROUGH A |
| | DOOR THAT IS NOT IDENTIFIED AS AN EXIT. |
| | |
| | 23. ON THE LIFE SAFETY SHEETS, SOME SLEEPING ROOMS ARE |
| | RATED AND EQUIPPED WITH FIRE DOORS AND OTHERS ARE NOT. |
| | PLEASE EXPLAIN RATIONALE. |
| | |
| | 24. PLEASE EXPLAIN CHILDREN'S/RECREATION (2-220) AREA. |
| | |
| | 25. ON THE FIRE SPRINKLER DRAWINGS CHECK VALVES FOR THE |
| | FIRE DEPARTMENT CONNECTIONS COULD NOT BE LOCATED. ALSO |
| | THE NEW FIRE HYDRANT IS TO BE LOCATED NO FARTHER THAN |
| | 150 FEET FROM THE FIRE DEPARTMENT CONNECTIONS. PLEASE |
| | EXPLAIN PURPOSE OF DRY FIRE DEPARTMENT CONNECTION |
| | LINES. |
| | |
| | 26. TAMPER SWITCHES, CHAIN AND LOCKS ARE REQUIRED ON |
| | FIRE LINE BACKFLOW DEVICE. |
| | |
| | 27. HOW WILL FURNITURE AND CLOTHING BE ARRANGED AND |
| | MAINTAINED AND PLEASE DOCUMENT STORAGE HEIGHTS IN THE |
| | STORAGE OR GROUP "S" BUILDING. |
| | |
| | 28. PLEASE INDICATE PURPOSE AND DURATION OF EXPECTED |
| | OCCUPANCY OF THE INTAKE AREAS. |
| | |
| | 29. THE PLANS SEEM TO SUGGEST SMOKE DETECTOR |
| | INSTALLATIONS WITH NO MENTION OF SMOKE ALARM |
| | INSTALLATIONS. SMOKE DETECTORS ARE USUALLY CONNECTED TO |
| | FIRE ALARM SYSTEMS AND SMOKE ALARMS ARE CONNECTED ONLY |
| | TO THE ELECTRICAL SYSTEM. PLEASE CLARIFY ALL SMOKE |
| | DETECTION EQUIPMENT. |
| | |
| | 30. SHEET FP-2 IS NOT VERY CLEAR. IT APPEARS THAT MORE |
| | THAN TWELVE FIRE SPRINKLER HEADS WILL BE NEEDED. |
| | |
| | 31. THE PLANS DO NOT SEEM TO CALL OR IDENTIFY |
| | PROTECTION FROM HAZARDS. ROOMS THAT CAN BE CONSIDERED |
| | MORE HAZARDOUS SUCH AS BOILER, FURNACE, ELECTRICAL |
| | ROOMS, ETC. NEED TO BE PROTECTED FROM OTHER PORTIONS OF |
| | THE BUILDINGS. PLEASE INDICATE HOW THIS IS BEING |
| | ACCOMPLISHED. |
| | |
| | 32. PLEASE REVIEW SECTION 310 OF THE FLORIDA BUILDING |
| | CODE FOR EXPLANATIONS OF R-1 AND R-2 OCCUPANCY TYPES. |
| | R-1 OCCUPANCIES ARE TRANSIENT AND R-2 OCCUPANCIES ARE |
| | PERMANENT. IT HAS BEEN SUGGESTED IN MEETINGS THAT |
| | OCCUPANCY AT THIS FACILITY IS MORE TRANSIENT IN NATURE |
| | (90) DAYS. |