| 2010-10-04 16:52:21 | ***************ELECTRICAL PLAN REVIEW | | | FAIL*************** | | | | | | 1) LIGHTING POWER DENSITIES REQUIRED FOR ALL NON | | | RESIDENTIAL AREAS OF ALL THREE BUILDINGS AS PER CHAPTER | | | 13 2007 FLORIDA BUILDING CODE | | | | | | 2) LIGHTING POWER DENSITIES REQUIRED FOR PARKING LOT | | | LIGHTING, AS PER CHAPTER 13 2007 FLORIDA BUILDING CODE | | | | | | 3) PLAN SHOWES PARALLEL FEEDS TO PANEL DH-3, EQUIPMENT | | | GROUNDING CONDUCTORS ARE REQUIRED TO BE FULL SIZE IN | | | EACH CONDUIT AS PER SIZE OF OVERCURRENT PROTECTIVE | | | DEVICE AS PER ARTICLE 250.122(F) 2008 NEC | | | | | | | | | JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE NUMBER | | | PX3182 | | | CELL NUMBER 561 718 3230 |
|