| 2010-09-28 17:00:37 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- A) BOTH SETS OF PLANS NEED TO BE SIGNED AND SEALED |
| | BY THE ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA |
| | ADMINISTRATIVE CODE.. ONLY ONE SET WAS SIGNED AND |
| | SEALED. |
| | |
| | B) ENGINEER TO HAVE HIS/HER ADDRESS ON THE TITLE BLOCK |
| | AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | |
| | A) GLASS BLOCK. |
| | |
| | B) WINDOW MULLIONS. AND, CLEARLY MARK ON DRAWINGS |
| | SPECIFIC MULLION SIZE AND FASTENERS TO BE USED TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | R301 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 4- REVISE THE ENERGY CALCULATIONS: |
| | A) R-19 INSULATION DOESN'T FIT ON 2X4 WALLS. REVISE |
| | INSULATION ON ITEM #9(A) AS REQUIRED. |
| | |
| | B) CLARIFY CAPACITY OF HOT WATER TANK. WHY 5 GALLONS |
| | ONLY? |
| | |
| | C) REVISE BUILDER NAME. SEE PERMIT APPLICATION FOR NAME |
| | OF CONTRACTOR. |
| | |
| | 5- SHEET 2.1: R-19 INSULATION DOESN'T FIT ON 2X4 WALLS. |
| | REVISE ALL DETAILS THAT SPECIFY R-19 ON THE 2X4 WALL. |
| | |
| | 6- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |