| Plan Review Notes For Permit 10080576 |
| Permit Number |
10080576 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-24 13:43:04 | 2031 PALM BEACH LAKES BOULEVARD | | | PERMIT NUMBER 10080576 | | | "COMMERCIAL INTERIOR ALTERATION" | | | | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. PROPER VENTILATION IS TO BE PROVIDED WHEN GASOLINE | | | POWERED EQUIPMENT IS USED INDOORS. CARBON MONOXIDE (CO) | | | IS A COLORLESS, ODORLESS, AND TASTELESS GAS THAT IS | | | FLAMMABLE IN THE PROPER CONCENTRATION. PROPER | | | VENTILATION CONTROLS ARE TO BE PROVIDED TO PREVENT THE | | | BUILD-UP OF CARBON MONOXIDE VAPORS. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 4. NEW ONE HOUR FIRE WALL IS TO BE PROPERLY IDENTIFIED | | | AND ALL OPENINGS BE PROTECTED. | | | | | | 5. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" | | | HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED ON THE | | | PROPER ELEVATION. NUMBERS ARE TO CONTRAST WITH THE | | | BACKGROUND THEY ARE AFFIXED TO. | | | | | | 6. INTERIOR WALL AND CEILING FINISHES IN EXITS AND EXIT | | | ACCESS CORRIDORS SHALL BE CLASS A OR B, NOT CLASS C. | | | | | | 7. WRONG EDITIONS OF FIRE CODES NOTED IN TITLE BLOCKS. | | | SHOULD READ 2006 EDITIONS NOT 2003 EDITIONS. | | | | | | 8. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|