| Plan Review Notes For Permit 10080537 |
| Permit Number |
10080537 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-02 07:27:53 | THE APPLICATION STATES THAT THERE IS N/A ADDITIONAL | | | COST FOR ADDITIONAL EQUIPMENT AND RACEWAYS INSTALLED. | | | | | | PLEASE SUBMIT CHANGE ORDER SHOWING COST FOR THIS | | | EQUIPMENT AND LABOR. | | | | | | FAN, FAN CONTROL, PANEL "A", ALL BREAKERS, WIRE TO | | | PANEL, 1" CONDUIT TO TELE RM. | | | | | | SUBMIT AIC CALCULATION FOR PANEL "A" SHOWING 10,000 |
|