| Plan Review Notes For Permit 10080410 |
| Permit Number |
10080410 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-01 10:28:11 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE WIND DESIGN CRITERIA ON THE PLANS. THE | | | STRUCTURE IS LOCATED IN A 14O MPH WIND SPEED AND | | | EXPOSURE CATEGORY C. FBC R301 | | | | | | 2) SPECIFY THE COMPONENT AND CLADDING OPENING PRESSURES | | | FOR THE WINDOWS AND DOORS ON THE PLANS. (WORST CASE | | | TRIBUTARY AREA 10 SQFT WITH 20 FT MEAN ROOF HEIGHT | | | +45.5, -60.8 PSF) FBC R301.2.1 | | | | | | 3) GENERAL NOTE 2 ON SHEET 1 SPECIFIES THAT ALL WINDOWS | | | ARE TO BE REPLACED WITH PGT IMPACT WINDOWS. THE PLANS | | | INDICATE AWNING WINDOWS AT THE DINING ROOM AND A | | | HORIZONTAL SLIDER AT THE LIVING ROOM. PLEASE SUBMIT 2 | | | SETS OF PRODUCT APPROVALS FOR THE AWNING WINDOWS AND | | | HORIZONTAL SLIDER AS REQUIRED BY DCA RULE 9B-72. | | | | | | 4) PRODUCT APPROVALS WERE SUBMITTED FOR PGT NON-IMPACT | | | RATED WINDOWS (NOA NO. 08-1112.09) AND PGT SMALL | | | MISSILE IMPACT RATED SINGLE HUNG WINDOWS (NOA NO. | | | 07-0306.11). BOTH OF THESE REQUIRED HURRICANE | | | PROTECTION DEVICES. PLEASE CLARIFY. | | | | | | 5) SHOW COMPLIANCE WITH FBC R313.2.1 FOR SMOKE ALARMS. | | | | | | 6) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | | COMMENTS HAVE BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|