| 2011-03-30 14:44:03 | REVIEW #: 2ND (FOR NEWLY DESIGNED BUILDING) |
| | ACTION:DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THESE COMMENTS ARE NUMBERED TO CORRESPOND WITH PREVIOUS |
| | REVIEW FOR CONTINUITY. ANY ADDITIONAL NEW COMMENTS WILL |
| | BE ADDED TO THE END OF THE REVIEW. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. EF-3 AND EF-5 ON PAGE M6-1 APPEAR TO HAVE THE ROOM |
| | NUMBER AND THE CFM REVERSED. PLEASE CORRECT TO |
| | CORRESPOND WITH THE FLOOR PLAN. FBC-M 304.11. |
| | |
| | 5. OK |
| | |
| | 6. OK |
| | |
| | 7. OK |
| | |
| | 8. OK |
| | |
| | 9. OK |
| | |
| | 10. OK |
| | |
| | 11. OK |
| | |
| | 12. OK |
| | |
| | 13. NOT ADEQUATELY ADDRESSED: FBC-M SECTION 404 |
| | REQUIRES A MINIMUM VENTILATION RATE OF 1.5 CFM/SQ.FT. |
| | THE VENTILATION RATE IS ALLOWED TO BE INTERMITTENT IF |
| | THE FAN IS CONTROLLED BY CARBON MONOXIDE SENSORS. PAGE |
| | M2-1 SHOWS THE FAN BEING CONTROLLED BY CARBON DIOXIDE |
| | SENSORS. THIS DOES NOT MEET THE REQUIREMENT OF THE CODE |
| | FOR AN ENCLOSED PARKING GARAGE. ALSO, SECTION 404 |
| | REQUIRES THAT IF INTERMITTENT VENTILATION IS USED, A |
| | MINIMUM CONTINUOUS VENTILATION RATE OF 0.05 CFM/SQ.FT |
| | BE PROVIDED. SHOW HOW THIS MINIMUM CONTINUOUS RATE IS |
| | TO BE PROVIDED. IN ADDITION, WHAT IS THE SIZE OF THE |
| | INTAKE LOUVER? NO SIZE IS GIVEN ON THE PLANS. THE SIZE |
| | MUST BE LARGE ENOUGH TO PROVIDE AT LEAST 1000 CFM OF |
| | MAKE-UP AIR FOR THE EXHAUST FAN BEING PROPOSED. |
| | |
| | NOTE: PROVIDE SIZES FOR ALL OUTDOOR LOUVERS. |
| | |
| | 14. NEW COMMENT: AHU-10 RETURN AIR SYSTEM IS |
| | REDESIGNED, ELIMINATING DUCTED RETURN AND UTILIZING |
| | TRANSFER DUCTS FROM OFFICES INTO ADJACENT HALL 37. |
| | THERE DOES NOT APPEAR TO BE A CENTRALIZED R/A INTAKE |
| | ASSOCIATED WITH AHU-10 LARGE ENOUGH TO DRAW ALL THE |
| | RETURN AIR FROM THESE TRANSFER DUCTS BACK TO THE AHU. |
| | PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN |
| | THIS AREA PER FBC-M 601.4. ALSO, THE TRANSFER DUCTS |
| | FROM THE OFFICE ARE NOT SIZED PER THE BALANCED RETURN |
| | AIR EXCEPTIONS UNDER FBC-M 601.4. THE TRANSFER DUCT |
| | MUST BE MINIMUM 1.5 TIMES THE SIZE OF THE SUPPLY DUCT. |
| | IN MOST CASES THE PLAN SHOWS A DUCT WITH APPROXIMATELY |
| | THE SAME SQUARE INCHES. SHOW HOW COMPLIANCE WITH FBC-M |
| | 601.4 IS TO BE ACHIEVED IN THESE AREAS. |
| | |
| | NOTE: THE KITCHEN HOOD EXHAUST SYSTEM IS EXCLUDED FROM |
| | THE SCOPE OF THIS REVIEW. SEPARATE PLANS AND PERMIT |
| | APPLICATIONS ARE REQUIRED FOR THE HOOD SYSTEM AND THE |
| | FIRE SUPPRESSION SYSTEM. |
| | |
| | |