| Plan Review Notes For Permit 10080396 |
| Permit Number |
10080396 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-24 09:16:21 | SHEET 053 E1-2 | | | PLEASE PROVIDE A SPECIFICATION FOR THE LIGHT POLE | | | DESIGN AND FOUNDATION. | | | | | | SHEET 055 E3-1 | | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES WITHIN 6 | | | FEET OF THE BAR SINK. NEC 210.8(B)(5) | | | | | | SHEET 056 E5-1 | | | MINIMUM SIZE SERVICE GROUNDING ELECTRODE CONDUCTOR HAS | | | BEEN MISLABELED ON THE RISER DIAGRAM. NEC T. 250.66 | | | PANEL A AND B FEEDER OVERCURRENT PROTECTION SHOULD BE | | | NO GREATER THAN THE PANELBOARD RATING. NEC 408.36 | | | | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | |
|