| Date |
Text |
| 2011-02-11 14:38:05 | BUILDING PLAN REVIEW |
| | PERMIT: 10080396 |
| | ADD: 2100 N FLORIDA MANGO |
| | CONT: TO BE DETERMINED |
| | CONTACT: PBA JOINT VENTURE INC |
| | TEL: (561)689-3745 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | FEB. 11/ 2011 |
| | 2ND REVIEW/ 1ST REVIEW OF 1 STORY BUILDING |
| | |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET: |
| | |
| | 1A) PLANS INDICATE THIS BUILDING TO BE FULLY FIRE |
| | SPRINKLERED BUT NO PLANS WERE SUBMITTED FOR THIS |
| | REVIEW. THE LIFE SAFETY REQUIREMENTS |
| | INDICATE THAT AREA INCREASES WERE TAKEN UNDER 2007 |
| | FBC-B 506.3. |
| | |
| | 1B) THE COVER SHEET LIFE SAFETY REQUIREMENTS UNDER THE |
| | HEADING OCCUPANCY INDICATE THIS TO BE A MIXED USE, |
| | NON-SEPARARTED OCCUPANCY. THE PLANS DO INDICATE A 1 |
| | HOUR RATED CORRIDOR FOR THE ASSEMBLY OCCUPANCY, BUT |
| | FAIL TO TAKE INTO ACCOUNT : |
| | 1B)(1) NO FIRE SPRINKLER PLANS SUBMITTED TO BE ABLE TO |
| | TAKE CREDIT FOR INCIDENTAL USE AREAS, (FBC-BTABLE 502). |
| | 1B)(2) THE PLANS DO NOT ADDRESS THE REQUIREMENTS FOR |
| | STORAGE ROOM > 100 SQ FT TO RESIST THE PASSAGE OF |
| | SMOKE, THE DOORS ARE TO BE SELF CLOSING OR AUTOMATIC |
| | CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE WITH |
| | SECTION 715.4.7.3. |
| | |
| | 1C)THE COVER SHEET LIFE SAFETY REQUIREMENTS UNDER THE |
| | HEADING OCCUPANCY INDICATE THIS TO BE A MIXED USE, |
| | NON-SEPARARTED OCCUPANCY. THE PLANS DO INDICATE A 1 |
| | HOUR RATED CORRIDOR FOR THE ASSEMBLY OCCUPANCY, BUT |
| | FAIL TO TAKE INTO ACCOUNT : |
| | 1B)(1) NO FIRE SPRINKLER PLANS SUBMITTED TO BE ABLE TO |
| | TAKE CREDIT FOR INCIDENTAL USE AREAS, (FBC-BTABLE 502). |
| | 1B)(2) THE PLANS DO NOT ADDRESS THE REQUIREMENTS FOR |
| | STORAGE ROOM > 100 SQ FT TO RESIST THE PASSAGE OF |
| | SMOKE, THE DOORS ARE TO BE SELF CLOSING OR AUTOMATIC |
| | CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE WITH |
| | SECTION 715.4.7.3. |
| | |
| | |
| | 2) SURVEY THE FLOOD DATA IS BLANK, FBC BUILDING |
| | 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A-9" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. MINIMUM |
| | ELEVATION FOR FINISH FLOOR TO BE ELEVATION 13'-6" NGVD. |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | MARCH 31, 2012. |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012. |
| | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| | MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS |
| | NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES |
| | MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED |
| | ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW |
| | FORM. |
| | |
| | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 3A) PLEASE REVIEW SP-1 THE PLANS INDICATE A PASSENGER |
| | LOADING ZONE VERSES A FLARED CURB 2007/ 2009 FBC-B |
| | 11-4.6.6 SEE FIGURE 11-10. |
| | PLEASE SEE 11-6.3 ACCESS AISLE SHALL BE STRIPED |
| | DIAGONALLY TO DESIGNATE IT AS A NO-PARKING ZONE.CURB |
| | RAMPS MUST BE LOCATED OUTSIDE OF THE DISABLED PARKING |
| | SPACES AND ACCESS AISLES. PLEASE BE AWARE OF 11-4.29.5 |
| | DETECTABLE WARNINGS AT HAZARDOUS VEHICLAR AREAS. |
| | |
| | 3B) SHEET SP-1 ALSO INDICATES 2 HANDICAPPED SPACES BUT |
| | THERE IS NO CUT DETAILS FROM THE ACCESS AISLE TO |
| | SIDEWALK AND CURB CUTS, SHEET SP-2 INDICATES TWO STYLES |
| | OF CURB CUTS, WHICH TYPE IS TO BE USED FOR THIS |
| | INSTALATION, PLEASE KEEP IN MIND CROSS SLOPE OF AN |
| | ACCESSIBLE ROUTE SHALL NOT EXCEED 1:50. 2007/ 2009 |
| | FBC-B 11-4.3.7. PLEASE BE AWARE OF 11-4.29.5 DETECTABLE |
| | WARNINGS AT HAZARDOUS VEHICLAR AREAS. |
| | |
| | 4) SHEET A-4.0; |
| | 4A) DETAILS 3 & 4 BOTH INDICATE THE USE OF GALVANIZED |
| | WIRE LATH OVER TYVAK WRAP, PLEASE REVIEW FBC-B 1404.2.1 |
| | NEW TO THE 2007 FBC A BOND BREAK WILL BE REQUIRED |
| | BETWEEN THE WIRE LATH AND TYVAK WRAP. PLEASE REVIEW THE |
| | THREE METHODS OF ACHIVING THIS, A PAPER BACK LATH AND |
| | TYVAK SYSTEM WILL ACHIEVE THIS REQUIREMENT. |
| | |
| | 4B) THE PLANS INDICATE THE USE OF USE OF HORIZONTAL |
| | RIB-LATH BEING ATTACHED TO METAL HIGH HAT, PLEASE |
| | PROVIDE TYPE OF FASTENER AND SPACING, FBC-B 2510.3. |
| | ASTM C 926 AND ASTM C 1063. |
| | |
| | 4C) R-19 UNFACED BATT INSULATION VERSES THE ENERGY |
| | CALCS CELOUSE R-20 INSULATION. PLEASE ALSO REVIEW A-8.2 |
| | THE REQUIREMENTSPACING FOR HIHAT WHEN INSULATION BATT |
| | OR BLANKET IS LAIDED DIRECTLY ON TOP OF THE HI-HAT. |
| | |
| | 5) SHEET A8-0 DETAIL# 3 A 1 HOUR RATED WALL DETAIL |
| | INDICATES THE ROOF DECK TO BE A METAL DECK, PLEASE |
| | CORRECT AND PROVIDE A DETAIL FOR SYSTEM UL DESIGN NO. |
| | HW-D-0011 . |
| | |
| | 6) THE PLANS DO NOT PROVIDE THE MEAN ROOF HEIGHT IN |
| | EITHER S.01 WIND DESIGN CRITERIA NOR ON S0.2 THE DESIGN |
| | PRESSURE TABLES, HAS THE HEIGHT FACTOR BEEN TAKEN INTO |
| | ACCOUNT IN THE DESIGN PRESSURES? |
| | |
| | 7) PRODUCT APPROVALS: |
| | 7A) FL 11727 PLEASE PROVIDE WHICH SUB-SYSTEM WILL |
| | INSTALLED CIRCLE SYSTEM. |
| | 7B) NOA 06-0417.09 PLEASE PROVIDE WHICH SUB-SYSTEM TO |
| | BE INSTALLED. NOTE ONLY PAGE 15 IS A NON-INSULATED ROOF |
| | THERE ARE THREE OPTIONS . OPTION# 1 HAS LOW PRESSURES |
| | AND LIMITATION #9. OPTIONS 2& 3 LIMITATION# 7 WHICH |
| | ALLOWS FOR ENHANCED FASTENING, PLEASE CICCLE WHICH |
| | SYSTEM TO BE INSTALLED ANAD PROVIDE CALCULATIONS FOR |
| | ZONES 2 & 3. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |