| 2010-09-01 15:07:38 | FBC PLUMBING 2007 |
| | REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEET A-2.2 FBC BUILDING 11-4.17.3 (2) THE |
| | ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE CORNER, |
| | DIAGONAL TO THE DOOR. WOMENS ROOM #213 |
| | |
| | 2.SHEET A-2.2 11-4.17.3 2ND FLOOR MENS ROOM #212 ADA |
| | COMPARTMENT DOES NOT CONFORM WITH FIGURE 30E TOILET |
| | STALL NEW CONSTRUCTION. |
| | |
| | 3. SHEET P 1.01 A - SHOWS ELEVATOR SUMP LINE CONNECTED |
| | TO THE SITE DRAINAGE. THE ELEVATOR SUMP SHALL NOT |
| | CONNECT TO THE SITE DRAINAGE DUE TO THE POSSIBILITY OF |
| | HYDRAULIC FLUID CONTAMINATION. ONE OPTION WOULD BE TO |
| | ROUTE THE PUMP LINE TO THE SANITARY THROUGH AN OIL |
| | INTERSEPTOR SIZED TO CONTAIN THE OIL |
| | FBC PLUMBING 701.4 SEWAGE TREATMENT. SEWAGE OR OTHER |
| | WASTE FROM A PLUMBING SYSTEM THAT IS DELETERIOUS TO |
| | SURFACE OR SUBSURFACE WATERS SHALL NOT BE DISCHARGED |
| | INTO THE GROUND OR INTO ANY WATERWAY UNLESS IT HAS |
| | FIRST BEEN RENDERED INNOCUOUS THROUGH SUBJECTION TO AN |
| | APPROVED FORM OF TREATMENT |
| | FBC BUILDING 3004.4 PLUMBING AND MECHANICAL SYSTEMS. |
| | PLUMBING AND MECHANICAL SYSTEMS SHALL NOT BE LOCATED IN |
| | AN ELEVATOR SHAFT. |
| | EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE |
| | PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE |
| | INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM. |
| | 701.5 DAMAGE TO DRAINAGE SYSTEM OR PUBLIC SEWER. WASTES |
| | DETRIMENTAL TO THE PUBLIC SEWER SYSTEM OR TO THE |
| | FUNCTIONING OF THE SEWAGE-TREATMENT PLANT SHALL BE |
| | TREATED AND DISPOSED OF IN ACCORDANCE WITH SECTION 1003 |
| | AS DIRECTED BY THE CODE OFFICIAL. |
| | |
| | 4. SHEET P 1.01B PLUMBING 314.2.2 CONDENSATE DRAIN PIPE |
| | MATERIALS AND SIZES. WHERE THE DRAIN PIPES FROM MORE |
| | THAN ONE UNIT ARE MANIFOLDED TOGETHER FOR CONDENSATE |
| | DRAINAGE, THE PIPE OR TUBING SHALL BE SIZED IN |
| | ACCORDANCE WITH AN APPROVED METHOD. 3/4" PIPE APPEARS |
| | TO BE TOO SMALL FOR 7 TONS OF CONDENSATE. |
| | A 3.0 ROOF DETAIL |
| | |
| | 5. SHEET P 1.02 B & P 2.01 THE CIRCUIT VENT FOR THE |
| | RESTROOMS REQUIRES A DRY VENT BETWEEN THE LAST TWO MOST |
| | UPSTREAM WC'S PLUMBING 911.2 VENT CONNECTION. THE |
| | CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN THE |
| | TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| | |
| | 6. SHEET P 2.01 4" SANITARY PIPE IS REQUIRED UP TO THE |
| | LAST 4 WATER CLOSETS. TABLE 710.1(2) |
| | |
| | 7. IRRIGATION PLAN - IF IRRIGATION IS CONNECTING TO THE |
| | DOMESTIC WATER SERVICE DOWNSTREAM OF THE RPZ BACKFLOW |
| | PREVENTOR, THE IRRIGATION LINE WILL REQUIRE A PRESSURE |
| | VACUUM BREAKER OR AN RPZ BACKFLOW PREVENTOR 608.16.5 |
| | |
| | ****NOTE***** FROM SHEET P1.01A - A SEPERATE |
| | APPLICATION, DRAWINGS, AND GAS PERMIT WILL BE REQUIRED |
| | FOR THE RELOCATED GENERATOR. |
| | |
| | REVIEW BY LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | (561) 805-6692 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | |