| 2010-09-14 18:26:50 | *****REVIEW COMMENTS - FIRE***** |
| | |
| | WATER PLAN 6 OF 9: SHIFT FIRE HYDRANT, BACKFLOW |
| | PREVENTER, AND FDC 30-FEET TO THE SOUTH TO AVOID |
| | DAMAGED FIRE PROTECTION EQUIPMENT IN A WALL COLLAPSE |
| | EVENT SINCE 40-FEET OF CLEARANCE CANNOT BE MAINTAINED |
| | BETWEEN THE BUILDING AND EQUIPMENT. POSSIBLE SHIFT MAY |
| | AFFECT LANDSCAPE PLANS. |
| | |
| | WATER PLAN 7 OF 9: ADDRESS SHOULD READ "2100 NORTH |
| | FLORIDA MANGO ROAD." |
| | |
| | WATER DETAILS 8 OF 9: BACKFLOW PREVENTER SHALL BE UL |
| | LISTED FOR FIRE PROTECTION SYSTEMS. PROVIDE TAMPER |
| | SWITCHES ON GATES VALVES. CHAIN/LOCK GATE VALVES IN |
| | OPEN POSITION. PROVIDE CHECK VALVE AND LOCKABLE KNOX |
| | CAPS ON FIRE DEPARTMENT CONNECTION. |
| | |
| | SHEET D-1.0: DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | |
| | SHEET LS-1: |
| | - FLORIDA FIRE PREVENTION CODE SHOULD BE THE 2007 |
| | EDITION. |
| | - DOOR SWINGS BLOCK MORE THAN 50% OF EXISTING CORRIDORS |
| | #116 AND #124 PER 7.2.1.4.4 OF NFPA 101. |
| | - NORTH STAIR INTERMEDIATE LANDING DECREASES IN WIDTH |
| | NEAR LOWER LANDING. |
| | - PROVIDE TACTILE SIGNAGE AT FIRST FLOOR EXITS. |
| | |
| | SHEET LS-2: IF BOTH DOORS OF ROOMS #219 AND #220 ARE |
| | OPEN AT THE SAME TIME, MORE THAN 50% OF THE GALLERY |
| | CORRIDOR IS OBSTRUCTED. |
| | |
| | SHEET A-2: |
| | - FESTIVAL SEATING IN ASSEMBLY OCCUPANCIES WITH |
| | OCCUPANT LOADS GREATER THAN 250 PERSONS REQUIRE AN |
| | APPROVED LIFE SAFETY EVALUATION PER 12.2.5.4 OF NFPA |
| | 101. |
| | - MOVEABLE CHAIRS ARE REQUIRED TO BE SECURED TOGETHER |
| | IN GROUPS OF 3-7 PER 12.7.9.1.1 OR IF CHAIRS ARE NOT |
| | SECURED TOGETHER, AN AREA OF 15 SQ.FT. PER SEAT IS |
| | REQUIRED PER 12.7.9.2.2 OF NFPA 101. |
| | - ASSEMBLY OCCUPANCIES GREATER THAN 250 OCCUPANTS |
| | REQUIRE CROWD MANAGERS PER 12.7.6 AND FIRE DRILLS PER |
| | 12.7.7 OF NFPA 101. |
| | - THE OCCUPANT LOAD OF THE ASSEMBLY SPACE SHALL BE |
| | POSTED NEAR THE MAIN ENTRANCE/EXIT OF THE ROOM PER |
| | 12.7.9.3 OF NFPA 101. |
| | |
| | SHEET E1.01A: MAIN ENTRANCE FEATURES A "REQUEST TO |
| | EXIT" BUTTON. ALL THE REQUIREMENTS OF 7.2.1.6.2 (NFPA |
| | 101) TO BE MET FOR ACCESS-CONTROLLED EGRESS DOORS. |
| | |
| | SHEET FA1.01A: |
| | - THE FIRE ALARM CONTROL PANEL (ELECTRICAL #136) IS |
| | SHOWN IN A DIFFERENT LOCATION FROM ELECTRICAL SHEET |
| | E1.02B (ROOM #216). COORDINATE LOCATION. |
| | - DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM CONDITION. |
| | - SMOKE DETECTOR AT TOP OF ELEVATOR SHAFT NOT PERMITTED |
| | UNLESS AUTOMATIC SPRINKLER IS PROTECTING TOP OF |
| | ELEVATOR SHAFT. |
| | |
| | GENERAL: |
| | - SIGNED/SEALED FIRE PROTECTION ENGINEERING DOCUMENTS |
| | PER FAC 61G15-32.001 ARE REQUIRED FOR A BUILDING |
| | PERMIT. |
| | - PROVIDE KNOX KEY SWITCH TO ALLOW FIRE DEPARTMENT |
| | ACCESS THROUGH ELECTRIC GATE |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | & WESLEY JOLIN |
| | WPB FIRE PLAN REVIEW |
| | 561-805-6730 |
| | |