| 2010-08-19 15:54:08 | 1000-45TH STREET |
| | HOMELESS RESOURCE CENTER |
| | PERMIT NUMBER 10080328 |
| | "INTERIOR DEMOLITION OF 3 EXISTING BUILDINGS, DRYWALL, |
| | FRAMING, ACOUSTIC, FLOORING, A/C, PLUMBING, ELECTRIC" |
| | |
| | |
| | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 2. DEBRIS SHALL BE REMOVED FROM THE STRUCTURES DAILY. |
| | |
| | 3. SUITABLE EXIT ACCESS AND EXITS SHALL BE PROVIDED |
| | DURING DEMOLITION ACTIVITIES. |
| | |
| | 4. ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY WITH |
| | NFPA 51B. WHEN CUTTING OR WELDING OPERATIONS OCCUR, A |
| | MINIMUM OF AT LEAST THIRTY FIVE (35) FEET OF CLEARANCE |
| | TO COMBUSTIBLES IS REQUIRED. IF NOT POSSIBLE TO ACHIEVE |
| | THIS SEPARATION, FIRE RATED MATERIALS MUST BE USED TO |
| | SHIELD THE COMBUSTIBLE MATERIALS FROM THE CUTTING OR |
| | WELDING OPERATIONS. PAY CLOSE ATTENTION TO WALL AND |
| | FLOOR OPENINGS SHOULD THIS ACTIVITY OCCUR. |
| | |
| | 5. SHOULD GASOLINE POWERED SAWS BE USED INSIDE, PROPER |
| | VENTILATIONS CONTROLS SHALL BE USED. CARBON MONOXIDE IS |
| | A COLORLESS, ODORLESS, AND TASTELESS GAS AND IS ALSO |
| | FLAMMABLE IN THE CORRECT CONCENTRATION. PROPER |
| | VENTILATION IS NECESSARY TO PREVENT CARBON MONOXIDE |
| | POISONING. |
| | |
| | 6. SUITABLE FIRE EXTINGUISHERS SHALL BE AVAILABLE FOR |
| | USE SHOULD THE NEED ARISE. |
| | |
| | 7. SUITABLE COMMUNICATION EQUIPMENT SHALL BE AVAILABLE |
| | TO REPORT EMERGENCIES TO EMERGENCY SERVICE |
| | ORGANIZATIONS. |
| | |
| | 8. DEMOLITION OF ELECTRICAL EQUIPMENT, SYSTEMS, AND |
| | DEVICES SHALL BE PERFORMED IN AN APPROVED AND IN A SAFE |
| | MANNER. |
| | |
| | 9. FIRE SEPARATION MATERIALS OR SYSTEMS SHOULD BE |
| | REMOVED TOWARDS THE END OF THE DEMOLITION TO PROVIDE |
| | FIRE CONTROLS SHOULD AN UNWANTED FIRE OCCUR. |
| | |
| | 10. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, |
| | AND AFTER CONSTRUCTION. |
| | |
| | APPROVED PROVISO |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |