2010-08-12 15:06:45*****REVIEW COMMENTS - FIRE*****
  
 1) VERIFY SYSTEM PRESSURES DO NOT EXCEED 100 PSI; 12"
 ARMOVERS SUBJECT TO PRESSURES IN EXCESS OF 100 PSI
 REQUIRE A HANGER.
  
 2) NOTE ON DRAWING THE THERMAL RESPONSE OF THE NEW
 SPRINKLERS.
  
 3) PLEASE EXPLAIN ARROW LEADER WITH NOTE "EXISTING
 PENDENT TO RELOCATE (TYP)" IN ELEVATOR LOBBY.
  
 4) CORRIDOR #729: SPRINKLERS SPACED 20'-0" APART.
  
 5) FILE ROOM #730: NO SPRINKLER COVERAGE IN NORTHERN
 PART OF ROOM.
  
 6) EMPLOYEE LOUNGE #711: SPRINKLERS SPACED 16'-0"
 APART.
  
 7) CUBICLE #739: SPRINKLER LOCATED 8'-2" FROM WEST
 WALL.
  
 NOTE: SPRINKLER WORK IS 47 SPRINKLERS BEFORE REVIEW
 COMMENTS ADDRESSED. ENGINEER'S SIGN AND SEAL REQUIRED
 FOR SPRINKLER WORK OF 50 OR MORE SPRINKLERS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730