| Plan Review Notes For Permit 10080313 |
| Permit Number |
10080313 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-12 15:06:45 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) VERIFY SYSTEM PRESSURES DO NOT EXCEED 100 PSI; 12" | | | ARMOVERS SUBJECT TO PRESSURES IN EXCESS OF 100 PSI | | | REQUIRE A HANGER. | | | | | | 2) NOTE ON DRAWING THE THERMAL RESPONSE OF THE NEW | | | SPRINKLERS. | | | | | | 3) PLEASE EXPLAIN ARROW LEADER WITH NOTE "EXISTING | | | PENDENT TO RELOCATE (TYP)" IN ELEVATOR LOBBY. | | | | | | 4) CORRIDOR #729: SPRINKLERS SPACED 20'-0" APART. | | | | | | 5) FILE ROOM #730: NO SPRINKLER COVERAGE IN NORTHERN | | | PART OF ROOM. | | | | | | 6) EMPLOYEE LOUNGE #711: SPRINKLERS SPACED 16'-0" | | | APART. | | | | | | 7) CUBICLE #739: SPRINKLER LOCATED 8'-2" FROM WEST | | | WALL. | | | | | | NOTE: SPRINKLER WORK IS 47 SPRINKLERS BEFORE REVIEW | | | COMMENTS ADDRESSED. ENGINEER'S SIGN AND SEAL REQUIRED | | | FOR SPRINKLER WORK OF 50 OR MORE SPRINKLERS. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|