2010-08-18 09:21:19BUILDING PLAN REVIEW
 PERMIT: 10080251
 ADD: 7105 NORTON AVE
 CONT: BCI COMMUNICATIONS
 TEL: (954)782-7092
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PE STEPHEN HEATH PLEASE REVIEW RULE 61G15-23.001
 THAT ELININATED THE USE OF THE WORD "CERTIFICATE"
 WITHIN THE SEAL IN DEC. 31/2005. THE CURRENT LANGUAGE
 WITHIN THE SEAL IS TO STATE "LICENSE".
  
 2) SHEET A3 INDICATES THE USE OF A FIBERCRETE SLAB AND
 DESIGNED BY OTHERS. PLEASE PROVIDE ENGINEERING FOR THIS
 SLAB, (FOUNDATION) THIS ENGINEERING IS TO BE REVIEWED
 BY THE ENGINEER OF RECORD BEFORE BEING PRESENTED TO THE
 BUILDING DEPARTMENT INCLUDING TTHE MOMENT OF
 OVERTURNING.SHEET A4 NOTE 11 INDICATES THE CONTRACTOR
 MAY USE AN APPROVED PRECAST EQUIVALENT, AGAIN THIS WILL
 NEED TO BE REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
 61G15-31.005 DESIGN OF STRUCTURES UTILIZING PRECAST AND
 PRESTRESSED CONCRETE COMPONENTS.
 (1) STRUCTURAL ENGINEERING DOCUMENTS SHALL INDICATE THE
 CONFIGURATION OF PRECAST AND PRESTRESSED COMPONENTS AND
 SHALL INCLUDE DETAILS OF SUPPORTS, ANCHORS AND
 CONNECTIONS FOR THOSE COMPONENTS.
 (2) THE ENGINEER OF RECORD FOR THE STRUCTURE MAY
 DELEGATE RESPONSIBILITY FOR THE DESIGN OF PRECAST OR
 PRESTRESSED CONCRETE COMPONENTS, OR SYSTEMS UTILIZING
 THOSE COMPONENTS, TO A DELEGATED ENGINEER. IN THAT CASE
 THE ENGINEER OF RECORD FOR THE STRUCTURE SHALL REQUIRE
 STRUCTURAL DELEGATED ENGINEERING DOCUMENTS FOR HIS
 REVIEW AS AN INDICATION THAT HIS INTENT HAS BEEN
 UNDERSTOOD AND THAT THE SPECIFIED CRITERIA HAVE BEEN
 USED. STRUCTURAL DELEGATED ENGINEERING DOCUMENTS SHALL
 BEAR THE IMPRESSED SEAL AND SIGNATURE OF THE DELEGATED
 ENGINEER.
 (3) STRUCTURAL DELEGATED ENGINEERING DOCUMENTS SHALL
 INCLUDE COMPONENT DETAILS, CALCULATIONS, AND
 FABRICATIONS AND ERECTION DRAWINGS. ALL SUCH SUBMITTALS
 SHALL IDENTIFY THE SPECIFIC PROJECT. THE EFFECT OF
 PRECAST AND PRESTRESSED CONCRETE MEMBERS ON OTHER PARTS
 OF THE BUILDING IS THE RESPONSIBILITY OF THE ENGINEER
 OF RECORD FOR THE STRUCTURE.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G) FS. HISTORY???NEW 1-26-93,
 FORMERLY 21H-31.005.
  
 3) THE STRUCTURAL MODIFICATION REPORTS SUBMITTED TO THE
 BUILDING DEPARTMENT ARE COPIES NOT THE ORIGINAL SIGNED
 AND SEAL DOCUMENTS.
 LANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved