| 2010-08-31 15:15:14 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ON SHEET SP-1 THE 2004 EDITION OF THE EXISTING |
| | BUILDING CODE IS SPECIFIED. PLEASE UPDATE TO THE 2007 |
| | EXISTING BUILDING CODE. |
| | |
| | 2) BASED ON THE 2009 REVISIONS TO THE FLORIDA BUILDING |
| | CODE RESIDENTIAL BECAUSE THE STRUCTURE IS LOCATED |
| | WITHIN 1500 FT OF EXPOSURE C TERRAIN, IT IS REQUIRED TO |
| | BE DESIGNED FOR EXPOSURE C. FBC R301.2.1.4.3. PLEASE |
| | REVISE SHEETS SP1, S1 AND S2. |
| | |
| | 3) PLEASE INCREASE THE WINDOW AND DOOR PRESSURES ON S2 |
| | TO REFLECT EXPOSURE C. FBCR301.2.1 |
| | |
| | 4) PLEASE UPDATE THE STRUCTURAL NOTES ON SHEET S-3 TO |
| | REFERENCE THE 2007 FBC AND ASCE7-05. |
| | |
| | 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE PGT |
| | IMPACT WINDOWS, THERMA-TRU IMPACT DOORS AND THE METAL |
| | ROOF SPECIFIED ON THE PLANS. DCA RULE 9B-72 |
| | |
| | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND EVALUATION REPORTS FOR THE ICYNENE |
| | SPRAY FOAM INSULATION. FBC R314 |
| | |
| | 7) THE PLANS INDICATE THAT THERE IS 3'-11" BETWEEN THIS |
| | STRUCTURE AND ANOTHER DWELLING UNIT LOCATED ON THE SAME |
| | PROPERTY. THE FIRE SEPARATION DISTANCE IS DEFINED AS |
| | THE DISTANCE FROM THE BUILDING FACE TO AN IMAGINARY |
| | LINE BETWEEN TWO BUILDINGS ON THE LOT. THEREFORE, THE |
| | FIRE SEPARATION DISTANCE IS 1' - 11 & 1/2" . SECTION |
| | 302.1 OF THE EXISTING BUILDING CODE REQUIRES PORTIONS |
| | OF A STRUCTURE THAT ARE BEING ALTERED TO COMPLY WITH |
| | THE FLORIDA BUILDING CODE. THE PLANS INDICATE THAT THE |
| | PORTION OF THE WALL WITH A FIRE SEPARATION DISTANCE OF |
| | LESS THAN 3 FEET IS BEING ALTERED TO ADD SOME WINDOWS. |
| | BASED ON FBCR TABLE R302.1, NO OPENINGS ARE ALLOWED IN |
| | THIS SECTION OF WALL. ALSO THE ALTERED WALL, NEW GABLE |
| | END AND UNDERSIDE OF THE OVER-HANG PROJECTION WILL |
| | REQUIRE A MINIMUM ONE HOUR FIRE-RESISTANCE RATING. |
| | PLEASE ADDRESS. |
| | |
| | 8) THE PLANS INDICATE THAT AN EXISTING STORAGE AREA |
| | WILL BE CONVERTED TO LIVING SPACE AT THE NEW BATHROOM. |
| | THIS WILL REQUIRE THE PLANS TO BE REVIEWED BY PALM |
| | BEACH COUNTY FOR IMPACT FEES. PLEASE INDICATE UNDER THE |
| | AREA CALCULATIONS ON THE PLANS THE SQUARE FOOTAGE OF |
| | THE STORAGE AREA THAT IS BEING CONVERTED TO LIVING |
| | SPACE. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R313.2.1 FOR REQUIRED SMOKE |
| | ALARMS. |
| | |
| | 10) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW |
| | EACH OF THE COMMENTS IS BEING ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |