| Plan Review Notes For Permit 10080211 |
| Permit Number |
10080211 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-11 11:53:26 | 900 SOUTH OLIVE AVENUE | | | ADD FIRE ALARM DEVICES TO THE EXISTING FIRE ALARM | | | SYSTEM AS DEPICTED ON THE DRAWING. | | | | | | | | | 1. VALUE APPEARS TOO LOW FOR THE SCOPE OF WORK. THE | | | GENERAL CONTRACTOR ADVISED THAT THE PERMIT VALUE SHOULD | | | HAVE BEEN AROUND $ 7,000.00 DOLLARS. IF CORRECT, THE | | | PLANS SHOULD HAVE BEEN SIGNED AND SEALED AND THE PERMIT | | | APPLICATION SHOULD REFLECT THIS VALUE. | | | | | | 2. NEW FIRE ALARM EQUIPMENT DISPLAYED HOWEVER EXISTING | | | EQUIPMENT NOT DISPLAYED. PLANS SHOULD REFLECT ENTIRE | | | FIRE ALARM SYSTEM BOTH NEW AND OLD EQUIPMENT. | | | | | | 3. ARE THERE ANY EXISTING OR NEW DUCT DETECTORS | | | PROVIDED IN THE BUILDING. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|