Plan Review Notes
Plan Review Notes For Permit 10080204
Permit Number 10080204
Review Stop E
Sequence Number 1
Notes
Date Text
2010-08-30 17:30:33********NOT ENOUGHT ELECTRICAL INFOMATION
 SUMITED**********
 1) NEED EXISTING BUILDING ELECTRIC SERVICE RISER
 DIAGRAM
 2) NEED LOAD CALCUATIONS FOR NEW REF. EQUIPMENT LOAD
 ONTO EXISTING ELECT. SERVICE
 3)ELECTRIC DIAGRAM SHOWING ALL CONDUIT AND WIRE SIZES
 FOR WIRING OF NEW EQUIPMENT
 JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE NUMBER
 PX3182
 CELL PHONE MUMBER 561- 718- 3230