2010-08-12 13:35:40BUILDING PLAN REVIEW
 PERMIT: 10080137
 ADD: 411 51ST ST
 CONT: CHECKMATE HOMES SERVICES
 TEL: (561)602-2465
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) R01.2.1.4 EXPOSUEW CATEGORY, SHEET A INDICATES THIS
 TO BE A "B" EXPOSURE, PLEASE REVIEW THE TYPE "C"
 EXPOSURE, THIS STRUCTURE IS LOCATED IN A "C" EXPOSURE.
  
 2) WITH THE "C" EXPOSURE PLEASE PROVIDE THE POSITIVE &
 NEGATIVE PRESSURES ASSOCIATED WITH THIS EXPOSURE
 (MULTIPLIER OF 1.15). PLEASE PROVIDE THE PRESSURES FOR
 THE INTERIOR ZONES AS WELL AS THE CORNER ZONES. TABLE
 R301.2(2) & TABLE R301.2(3).
  
 3) THE PLANS INDICATE A STRAPPING DETAIL FOR A TYPICAL
 WINDOW BUT DO NOT PROVIDE THE STRAPPING FOR THE 12'-0"
 WIDE OPENING. THE OTHER ISSUE WITH THIS OPENING IS THE
 AMOUNT OF FULL LENGTH STUDS AND JACK STUDS THAT ARE
 REQUIRED, THE PLANS DO NOT FEFLECT AN ACCURATE CORNER
 AND CONNECTION TO THE MWFRS.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) THE LAWSON WINDOWS SUBMITTED NOA: 09-0720.05 ARE A
 NON-IMPACT UNIT THAT WILL REQUIRE STORM SHUTTERS.
 PLEASE SUBMIT THE SHUTTER PRODUCT APPROVAL WITH THE
 FOLOWING:
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 PLEASE PROVIDE ANCHORING AND SYSTEM WHICH WILL ALLOW
 FOR THE REQUIRED SEPERATION FROM GLAZING TO SHUTTER
 SINCE THE WINDOWS ARE A FLANGE MOUNT TYPE WINDOW.
  
 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 6A) STORM SHUTTERS OR PANELS RULE 9B-72(31) (E)
  
 6B) ROOFING ASSEMBLIES RULE 9B-73(31) (D)
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved