Plan Review Notes
Plan Review Notes For Permit 10080045
Permit Number 10080045
Review Stop M
Sequence Number 1
Notes
Date Text
2010-08-13 16:28:53****CORRECTIONS****
  
 1. MECHANICAL PLAN DOES NOT PROVIDE INFORMATION SUCH AS
 DUCT LAYOUT, SIZE, NEW WORK, EXISTING, RETURNS,
 EQUIPMENT, ETC. PROVIDE A COMPLETE MECHANICAL PLAN FOR
 REVIEW.
  
 2. NEW UNDER AIR SQUARE FOOTAGE SHOWN. INFORMATION
 REGARDING HOW THIS AREA WILL BE CONDITIONED (DUCTWORK,
 INFO REGARDING EXISTING UNIT, NEW SQUARE FOOT AREA,
 ETC.) TO BE PROVIDED. SHOW HOW IT HAS BEEN DETERMINED
 THAT THE EXISTING UNIT CAN ACCOMODATE THE NEW UNDER AIR
 SQUARE FOOTAGE.
  
 3. MECHANICAL SHEETS DO NOT MATCH ARCHITECTURALS. FOR
 INSTANCE, SEE MASTER BEDROOM, MASTER BATH, WARDROBE -
 COMPARE SHEETS A3, M1.02.
  
 4. ENERGY CALCS REQUIRED FOR ADDITIONAL SQUARE FOOT
 AREA, FBC 13-101.
  