| Plan Review Notes For Permit 10080045 |
| Permit Number |
10080045 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-13 16:28:53 | ****CORRECTIONS**** | | | | | | 1. MECHANICAL PLAN DOES NOT PROVIDE INFORMATION SUCH AS | | | DUCT LAYOUT, SIZE, NEW WORK, EXISTING, RETURNS, | | | EQUIPMENT, ETC. PROVIDE A COMPLETE MECHANICAL PLAN FOR | | | REVIEW. | | | | | | 2. NEW UNDER AIR SQUARE FOOTAGE SHOWN. INFORMATION | | | REGARDING HOW THIS AREA WILL BE CONDITIONED (DUCTWORK, | | | INFO REGARDING EXISTING UNIT, NEW SQUARE FOOT AREA, | | | ETC.) TO BE PROVIDED. SHOW HOW IT HAS BEEN DETERMINED | | | THAT THE EXISTING UNIT CAN ACCOMODATE THE NEW UNDER AIR | | | SQUARE FOOTAGE. | | | | | | 3. MECHANICAL SHEETS DO NOT MATCH ARCHITECTURALS. FOR | | | INSTANCE, SEE MASTER BEDROOM, MASTER BATH, WARDROBE - | | | COMPARE SHEETS A3, M1.02. | | | | | | 4. ENERGY CALCS REQUIRED FOR ADDITIONAL SQUARE FOOT | | | AREA, FBC 13-101. | | | | | | HAROLD MOSER, 805-6732 | | | | | | | | | |
|