| 2010-08-17 19:26:49 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. ARCHITECTURAL SHEET A3 DOES NOT MATCH MECHANICAL |
| | FLOOR PLAN, SEE MASTER BEDROOM. |
| | |
| | 2. PROVIDE THE TOTAL SQUARE FOOT AREA UNDER AIR |
| | PROPOSED. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY, |
| | 233-5025. THE PLANS ARE TO BE STAMPED AND THE RECEIPT |
| | (IF FEES ARE DUE) PROVIDED. |
| | |
| | 3. THIS PARCEL IS LOCATED IN A FLOOD ZONE. FINISHED |
| | FLOOR IS REQUIRED TO BE 6" ABOVE BFE (WPB ADMIN CODE |
| | 94-546(B)*. |
| | |
| | 4. PROVIDE A SIGNED AND SEALED FLOOD ELEVATION |
| | CERTIFICATE FOR THE PROPOSED CONSTRUCTION |
| | (HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM). THREE |
| | ELEVATION CERTIFICATES WILL REQUIRED; PRE CONSTRUCTION, |
| | FORM BOARD, AND FINISHED FLOOR. |
| | |
| | 5. PROVIDE A COST BREAKDOWN OF THE PROPOSED |
| | IMPROVEMENT. AS PROPOSED ELEVATIONS WERE NOT PROVIDED, |
| | AND A COST BREAKDOWN (ADDITION VS. RENOVATION AREAS) IT |
| | IS NOT CLEAR WHETHER OR NOT THIS IS A SUBSTANTIAL |
| | IMPROVEMENT, WPB ADMIN CODE 94-546. SEE ALSO HTTP://WWW |
| | .FEMA.GOV/PLAN/PREVENT/FLOODPLAIN/NFIPKEYWORDS/SI.SHTM |
| | FOR MORE INFORMATION. |
| | |
| | 6. SEE FBC EXISTING BUILDING 401.4, A DESIGN |
| | PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| | COMBINATION OF LEVELS OF ALTERATION. PLEASE INCLUDE |
| | THIS INFORMATION ON THE PLAN. PLEASE REVIEW ALL |
| | REQUIREMENTS (AND ALSO CH 10, ADDITIONS) AND SHOW |
| | COMPLIANCE ON THE PLAN. |
| | |
| | 7. PROVIDE A COPY OF THE SURVEY FOR THIS PARCEL. |
| | |
| | 8. PRODUCT APPROVAL REQUIRED FOR THE SIDING AND ROOF. |
| | THE ROOF PRODUCT APPROVAL MAY BE SUBMITTED WITH THE |
| | ROOF PERMIT. |
| | |
| | 9. STUCCO IS SHOWN AS 5/8" ON SHEET A8, SEE INSPECTION |
| | FOR TERMITES 704.1 EXCEPTION 1. |
| | |
| | 10. PROVIDE ENERGY CALCS, FBC 13-6. |
| | |
| | 11. SMOKE AND CARBON MONOXIDE ALARMS ARE REFERENCED ON |
| | E3 BUT NOT SHOWN ON PLAN, PLEASE SHOW ALL REQUIRED ON |
| | THE PLAN. |
| | |
| | 12. SEE FS 553.844 REGARDING ROOF MITIGATION |
| | REQUIREMENTS AND OPENING PROTECTION REQUIREMENTS AND |
| | SHOW COMPLIANCE ON THE PLAN. CLARIFY SCOPE OF REROOF |
| | AREA. |
| | |
| | 13. SEE FBC R301.2.1.4.3 (2), EXPOSURE C: BUILDINGS |
| | LOCATED WITHIN A DISTANCE OF 600 FEET OF INLAND BODIES |
| | OF WATER THAT PRESENT A FETCH OF 1 MILE (1.61 KM) OR |
| | MORE OR INLAND WATERWAYS OR RIVERS WITH A WIDTH OF 1 |
| | MILE (1.61 KM) OR MORE SHALL BE CLASSIFIED AS EXPOSURE |
| | C AND ROOF SHEATHING UPLIFT AND ROOF-TO-WALL UPLIFT |
| | LOADS SHALL BE INCREASED BY 20 PERCENT. |
| | |
| | |