| 2010-08-02 16:02:35 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE INFORMATION SHOWING WHAT'S THE TESTED | | | ATTACHMENT RESISTANCE VALUE OF THE TILE WHEN USING THE | | | POLYPRO AH160. NEITHER THE TILE NOA OR THE FOAM NOA | | | PROVIDE THIS INFORMATION. NEED INFORMATION TO VERIFY | | | COMPLIANCE WITH THE UPLIFT LOADS OF SEC. R301. | | | | | | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|