Plan Review Notes
Plan Review Notes For Permit 10080007
Permit Number 10080007
Review Stop B
Sequence Number 1
Notes
Date Text
2010-08-02 12:14:30RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1219.09 SUBMITTED. NEED RAS 117 CALCULATIONS TO MEET
 THE DESIGN PRESSURES OF SEC. R301.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS
 BUILDING IS LOCATED ON EXPOSURE 'C". SEC. R301.2.1.4.3
 OF 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE.
  
 2- ACCORDING TO THE MIAMI-DADE WEBSITE POLYSTICK NOA
 08-0929.03 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
  
 4- OWES $54.99 FOR UPDATED VALUATION AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712