| 2010-08-12 12:51:20 | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) R319.1 LOCATION REQUIRED. PROTECTION FROM DECAY |
| | SHALL BE PROVIDED IN THE FOLLOWING |
| | LOCATIONS BY THE USE OF NATURALLY DURABLE WOOD OR WOOD |
| | THAT IS PRESERVATIVE TREATED IN |
| | ACCORDANCE WITH AWPA U1. |
| | (5). WOOD SIDING, SHEATHING AND WALL FRAMING ON THE |
| | EXTERIOR OF A BUILDING HAVING A |
| | CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE |
| | GROUND. |
| | |
| | 2) R703.6.3 WHERE CEMENT PLASTER (STUCCO) IS TO BE |
| | APPLIED TO LATH OVER FRAME |
| | CONSTRUCTION, MEASURES SHALL BE TAKEN TO PREVENT |
| | BONDING BETWEEN THE CEMENT PLASTER |
| | AND THE WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE |
| | PROVIDED BETWEEN THE WATER- |
| | RESISTIVE BARRIER AND THE CEMENT PLASTER (STUCCO) |
| | CONSISTING OF ONE OF THE FOLLOWING: |
| | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER |
| | MATERIAL; OR |
| | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE |
| | WRAP; OR |
| | 3.OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | |