| Plan Review Notes For Permit 10070806 |
| Permit Number |
10070806 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-02 10:38:34 | 222 LAKEVIEW AVENUE, SUITE 1510 | | | PERMIT NUMBER 10070806 | | | | | | | | | 1. NO INFORMATION PROVIDED ON ANY NEW OR EXISTING FIRE | | | SPRINKLER SYSTEM EQUIPMENT OR DEVICES. | | | | | | 2. COULD NOT LOCATE ANY NEW OR EXISTING FIRE ALARM | | | EQUIPMENT WITHIN TENANT SPACE. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 6. EXITS ARE TO BE MAINTAINED DURING CONSTRUCTION. | | | | | | | | | DENIED | | | | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | | | | |
|