Plan Review Notes
Plan Review Notes For Permit 10070806
Permit Number 10070806
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-08-02 10:38:34222 LAKEVIEW AVENUE, SUITE 1510
 PERMIT NUMBER 10070806
  
  
 1. NO INFORMATION PROVIDED ON ANY NEW OR EXISTING FIRE
 SPRINKLER SYSTEM EQUIPMENT OR DEVICES.
  
 2. COULD NOT LOCATE ANY NEW OR EXISTING FIRE ALARM
 EQUIPMENT WITHIN TENANT SPACE.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 6. EXITS ARE TO BE MAINTAINED DURING CONSTRUCTION.
  
  
 DENIED
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  