| Plan Review Notes For Permit 10070802 |
| Permit Number |
10070802 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-18 14:41:54 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) PER FLORIDA STATUES 471 AND F.A.C. 61G15-23.002, THE | | | SLAB AND ANCHORING FOR WINDLOAD FROM THE ENGINEER, | | | RONALD WILSON, IS REQUIRED TO HAVE THE ORIGINAL | | | SIGNATURE AND SEAL OF THE ENGINEER AND THE DATE THAT HE | | | SIGNED AND SEALED THE DRAWINGS. | | | | | | 2) THE EXPOSURE CATEGORY IS INCORRECT ON THE PLANS. IT | | | IS LOCATED IN EXPOSURE CATEGORY C. PLEASE CORRECT. | | | | | | 3) PER NFPA 37, THE GENERATOR MUST BE LOCATED A MINIMUM | | | OF 5 FEET FROM OPENINGS IN WALLS AND 5 FEET FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS. GENERATORS SHALL | | | BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS AND NFPA 37. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|