| 2010-09-22 19:18:34 | ELECTRICAL PLAN REVIEW COMMENTS - 10070788 |
| | 9/21/2010 |
| | DOUG WISE, 805-6650, [email protected] |
| | |
| | 1. SHEET E0.02 NOTES 20 AND 21 - PLEASE NOTE THE DESIGN |
| | MUST SATISFY THE FOLLOWING CRITERIA: |
| | 13-413.ABC.1.1 FEEDERS AND CUSTOMER-OWNED SERVICE |
| | CONDUCTORS. FEEDER AND CUSTOMER-OWNED SERVICE |
| | CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF |
| | 2 PERCENT AT DESIGN LOAD. |
| | 13-413.ABC.1.2 BRANCH CIRCUITS. BRANCH CIRCUIT |
| | CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF |
| | 3 PERCENT AT DESIGN LOAD. |
| | THIS DESIGN RESPONSIBILITY CANNOT BE TRANSFERRED TO THE |
| | ELECTRICAL CONTRACTOR. THE DESIGN PROFESSIONAL SHALL |
| | PROVIDE A TABLE WITH WIRE SIZES AND MAXIMUM WIRE |
| | LENGTHS OR OTHER MEANS TO ENSURE THE DESIGN ITSELF |
| | SATISFIES THIS CRITERIA. |
| | |
| | 2. SHEET E0.02 NOTE 39 - MULTIWIRE BRANCH CIRCUITS MAY |
| | BE PERMITTED IF THEY SHARE A COMMON BREAKER OR HANDLE |
| | TIE, FURTHER ALL CONDUCTORS SHALL BE "TIED" THAT SERVE |
| | SUCH A MULTI-WIRE BRANCH CIRCUIT WITHIN THE PANELBOARD |
| | PURSUANT TO SECTION 210.4(D). |
| | |
| | 3. SHEET E2.01 - PROVIDE A PLAN WHICH DEMONSTRATES THE |
| | REQUIRED OPENING(S) AND RELATED ELECTRICAL FIXTURES FOR |
| | THE BREAK ROOM |
| | |
| | 4. SHEET E2.01 - PROVIDE POWER DENSITY TABULATIONS OR |
| | OTHER DATA TO DEMONSTRATE COMPLIANCE WITH |
| | FBC13-415.ABC.5 |
| | |
| | 5. SHEET E2.02 - PROVIDE POWER DENSITY TABULATIONS OR |
| | OTHER DATA TO DEMONSTRATE COMPLIANCE WITH |
| | FBC13-415.ABC.5 |
| | |
| | 6. SHEET E2.03 - PROVIDE POWER DENSITY TABULATIONS OR |
| | OTHER DATA TO DEMONSTRATE COMPLIANCE WITH |
| | FBC13-415.ABC.5 |
| | |
| | 7. SHEET E3.01 - VENDING EQUIPMENT OR RECEPTACLES MUST |
| | COMPLY WITH NEC 422.51 |
| | |
| | 8. SHEET E3.02 - SERVER ROOM MUST COMPLY WITH NEC 645.4 |
| | AND 645.10 INCLUDING FIRE RATED SEPARATION, |
| | ELECTRICALLY CONTROLLED DAMPERS, AND DISCONNECTING |
| | MEANS FOR SEPARATE HVAC AND EQUIPMENT. PLEASE |
| | DEMONSTRATE COMPLIANCE AND COORDINATE DESIGN WITH OTHER |
| | RELATED PLAN PAGES. |
| | |
| | 9. SHEET E3.02 - DRINKING FOUNTAIN CIRCUIT MUST BE GFI |
| | PROTECTED PURSUANT TO NEC 422.52. PLEASE COORDINATE |
| | WITH E7.03 PANEL SCHEDULE 2TB |
| | |
| | 10. SHEET E3.02 - ONLY TWO "SMALL APPLIANCE" BRANCH |
| | CIRCUITS ARE SHOWN FEEDING THE BREAK ROOM COUNTER. IF A |
| | MICROWAVE OVEN AND A COFFEE MACHINE ARE DESIRED, |
| | ADDITIONAL DEDICATED CIRCUITS MAY BE REQUIRED TO |
| | ADEQUATELY SERVICE THIS LOCATION. PLEASE VERIFY THESE |
| | REQUIREMENTS WITH THE CUSTOMER. |
| | |
| | 11. SHEET E3.03 - PLEASE REVIEW RECEPTACLE LOCATIONS IN |
| | THE BREAK ROOM. IT APPEARS INSUFFICIENT RECEPTACLES |
| | HAVE BEEN SHOWN AND ARE BEING SHOWN IN THE WRONG |
| | LOCATIONS. PLEASE REVIEW CUSTOMER NEEDS IN |
| | CONSIDERATION OF COMMENT #10 ABOVE. ENSURE ADEQUATE |
| | CIRCUITS ARE PROVIDED TO SATISFY CUSTOMER'S NEEDS. |
| | |
| | 12. SHEET E5.01 - RISER INDICATES TENANT SPACE IS TO BE |
| | SERVED BY SEPARATE 15 ELECTRICAL METERS AND SERVICES. |
| | PLEASE VERIFY THAT THIS IS THE ACTUAL DESIGN INTENT. |
| | SHEET A2.01, NOTE 2 INDICATES THE CONTRACTOR IS TO |
| | PERMIT AND INSTALL AN EMERGENCY GENERATOR. ALTHOUGH AN |
| | EMERGENCY GENERATOR WILL BE PERMITTED SEPARATELY, |
| | ADEQUATE PROVISION IN THE ELECTRICAL SERVICE DESIGN IS |
| | NECESSARY TO FACITILATE THIS INTENT. PLEASE RECONCILE |
| | THESE INTENTIONS OR CLARIFY. |
| | |
| | 13. SHEET E5.01 - IT APPEARS THAT PANEL 2SR IS BEING |
| | FED FROM METER 2ST. PLEASE CLARIFY OR RECONCILE. |
| | |
| | 14. SHEET E5.02 - PLEASE NOTE THAT SEPARATE |
| | APPLICATION, REVIEW AND PERMITTING IS REQUIRED FOR FIRE |
| | ALARM AND ACCESS CONTROL SYSTEMS PROPOSED WITHIN THIS |
| | STRUCTURE. A SEPARATE "SUB-PERMIT" SHALL BE REQUIRED |
| | FOR ALL CATV / TELECOM / LOW VOLTAGE SYSTEMS NOT |
| | PERFORMED DIRECTLY BY THE "PRIME" ELECTRICAL |
| | CONTRACTOR. |
| | |
| | 15. SHEET E6.01 - PLEASE NOTE THAT PURSUANT TO NEC |
| | ARTICLE 285 AND SECTION 285.5 ALL SURGE PROTECTION |
| | DEVICES (SPDS) SHALL BE LISTED. DEVICES BEARING THE |
| | TVSS DESIGNATION MAY NOT BE LISTED. ALSO PLEASE REVIEW |
| | SECTION 285.12 WHICH GOVERNS THE ROUTING OF CONNECTIONS |
| | BETWEEN THE SPD AND THE BUS. DESIGN DOCUMENTS SHOULD |
| | DESIGNATE SPDS AS TYPE 1, TYPE 2, AND TYPE 3 TO |
| | FACILITATE COMPLIANCE WITH ARTICLE 285. |
| | |
| | 16. SHEET E7.01 - PLEASE NOTE MY PREVIOUS COMMENT UNDER |
| | NOTE 1 (ABOVE) REGARDING VOLTAGE DROP AND |
| | RESPONSIBILITY FOR THE DESIGN TO SATISFY THE CODE |
| | CRITERIA. |
| | |
| | 17. SHEET E7.01 - THE ELECTRICAL PLANS APPEAR TO BE |
| | LACKING A "SPECIAL PURPOSE RECEPTACLE SCHEDULE" TO |
| | INDICATE WHAT DEVICES WILL BE ATTACHED TO THE NUMBERED |
| | SPECIAL PURPOSE RECEPTACLES SHOWN ON THE THREE |
| | ELECTRICAL FLOOR PLANS. SHEET E7.01 MIGHT BE AN |
| | APPROPRIATE LOCATION FOR SUCH A SCHEDULE. |
| | |
| | 18. SHEET ED2.04 NOTE 6 - NO EQUIPMENT IS TO BE |
| | ENERGIZED WITH THE WRITTEN CONSENT OF THE CITY |
| | ELECTRICAL INSPECTOR. NO WORK IS TO BE PERFORMED ON |
| | ENERGIZED EQUIPMENT. AFTER HOURS INSPECTIONS ARE |
| | AVAILABLE UPON REQUEST TO FACILITATE COORDINATION OF |
| | INSPECTION AND MINIMIZE ADVERSE IMPACTS. |
| | |
| | 19. SHEET ED2.04 NOTE 9 - ALL TEMPORARY ELECTRICAL |
| | SYSTEMS ARE TO BE DOCUMENTED, REVIEWED, INSPECTED AND |
| | FOUND TO BE IN FULL COMPLIANCE WITH ARTICLE 590 OF THE |
| | NEC BEFORE UTILIZATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME DIRECTLY WITH CONCERNS |
| | OR QUESTIONS ABOUT THIS REVIEW. |
| | |
| | I MAY BE REACHED DURING NORMAL BUSINESS HOURS AT THE |
| | NUMBER SHOWN AT TOP OR BY EMAIL. |
| | |
| | DOUG WISE |
| | |
| | |
| | |
| | |
| | |