2011-07-12 11:58:30SOLAR STAR ATTIC FAN PRODUCT APPROVAL REVIEW ONLY:
  
 BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 REVIEWED PRODUCT APPROVAL DOCUMENTS SUBMITTED 6/28/11.
 PLEASE SUBMIT WIND PRESSURE TEST DATA AS REQUESTED IN
 THE FOLLOWING EMAIL SENT TO THE PRODUCT MANUFACTURER
 AND DISTRIBUTOR:
  
 I HAVE BEEN GIVEN A COPY OF YOUR EMAIL CORRESPONDENCE
 THAT STATES THAT THE SOLATUBE INTERNATIONAL, INC., 14"
 SOLAR STAR ATTIC FAN WILL BE UNDERGOING TESTING TO TEST
 APPLICATION STANDARD TAS 100(A) - 95 IN JULY 2011.
 PLEASE PROVIDE RESULTS FROM THOSE TESTS AS SOON AS
 POSSIBLE SO THAT WE CAN ISSUE A PERMIT BASED ON FLORIDA
 STATE PRODUCT APPROVAL # FL10884. THE PRODUCT HAS BEEN
 USED AT A PROPERTY HERE IN WEST PALM BEACH, FL, AND
 THERE IS NO JUSTIFICATION IN THE FLORIDA PRODUCT
 APPROVAL DOCUMENTATION OR ANY OTHER SOURCE TO SUPPORT
 ITS USE IN A RESIDENCE WHERE THE DESIGN WIND SPEED IS
 140 MPH (3 SECOND GUST) AND THE EXPOSURE CATEGORY IS C.
 WE NEED TO HAVE THE TAS 100(A) -95 TEST RESULTS OR SOME
 OTHER DOCUMENTATION SHOWING SUCCESSFUL TESTING FOR
 PRESSURES ASSOCIATED WITH A DESIGN WIND SPEED OF 140
 MPH (3 SECOND GUST), EXPOSURE CATEGORY C, IN TIME FOR A
 JULY 29 MAGISTRATE HEARING, OR THE PROPERTY OWNER'S
 WILL HAVE TO REQUEST AN EXTENSION WHICH MAY OR MAY NOT
 BE GRANTED BY THE MAGISTRATE.
  
 WE ACKNOWLEDGE AND ACCEPT THE FACT THAT THE PRODUCT IS
 COVERED BY FLORIDA STATE PRODUCT APPROVAL # FL10884. WE
 WILL PASS THE INSTALLATION PROVIDED WE CAN ESTABLISH
 THAT THE PRODUCT HAS BEEN TESTED TO A WIND DESIGN
 PRESSURE THAT EXCEEDS THAT WHICH IS CALCULATED FOR THE
 LOCATION AT WHICH THE PRODUCT IS INSTALLED. THE FLORIDA
 STATE PRODUCT APPROVAL # FL10884 DOES NOT STATE THE
 DESIGN WIND PRESSURE. THE SUPPORTING DOCUMENTATION FROM
 PAUL WINTER, P.E., AFFIRMS THAT THE PRODUCT WAS TESTED
 TO ASCE 7-02 AND THAT THE TESTING MEETS THE
 REQUIREMENTS OF THE CURRENT 2007 FLORIDA BUILDING CODE.
 HOWEVER THE WIND DESIGN WIND SPEEDS REQUIRED TO SHOW
 COMPLIANCE WITH THE REQUIREMENTS OF THE CURRENT 2007
 FLORIDA BUILDING CODE VARY BASED ON THE SIZE OF THE
 BUILDING AND ITS GEOGRAPHIC LOCATION IN THE STATE OF
 FLORIDA. A PRODUCT WHICH COMPLIES WHEN USED IN CENTRAL
 FLORIDA MAY NOT COMPLY WHEN USED IN COASTAL REGIONS.
 THE WEST PALM BEACH DESIGN WIND SPEED IS NOT QUITE AS
 HIGH AS MIAIMI-DADE BUT IT IS CLOSE AT 140 MPH.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652 ROBERT BROWN