2011-02-23 10:03:41BUILDING PLAN REVIEW
 PERMIT: 10070762
 ADD: 8000 VIA VILLAGIO
 CONT: SDI SOLAR INC
 TEL: (561)722-3088
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 FEB. 23/ 2011
 ACTION: DENIED
  
 1) THE SOLAR ROOF POWERED ROOF VENTILATION FAN DOES
 HAVE A CURRENT FLORIDA APPROVAL UNDER THE 2007 FBC. THE
 SUBMITTAL THAT IS REFRENECING THE 14 INCH SOLAR STAR
 VENT AND LETTER OF EQIVALENCY REFRENCES THE ORIGINAL
 TEST WHICH EAS CONDUCTED UNDER 110 FASTEST MILE. IN
 2001
 WE USED ASCE7 98 110 FASTEST MILE. THE 2004 FBC THEN
 WENT TO ASCE 7-02 WHICH WAS A 3 SECOND GUST AND WIND
 SPEED OF 140 MPH.
 2004 FBC-B TABLE 1609.3.1 PROVIDES THE EQUIVALENT WIND
 SPEEDS BETWEEN V3S & VFM. FOR OUR WIND SPEED ZONE OF
 140 MPH (3 SECOND GUST) THE EQUIVALENT VFM WOULD BE
 120, NOT 140. THIS UNIT DOES HAVE A FLORIDA APPROVAL
 BUT SHOULD NOT BE PERMITTED NAD INSTALLED WHERE THE
 WIND SPEEDS ARE GREATER THAN 120 3S GUST.
  
 I SPOKE WITH OUR ASST. BUILDING OFFICIAL AND NO LOCAL
 APROVAL CAN BE APPLIED FOR UNLESS AN ENGINEER WILL
 PROVIDE DOCUMENTATION WHERE THE MODEL IN QUESTION CAN
 PRODUCE DOCUMENTATION FOR COMPLIANCE WITH 140 3 SECOND
 GUST. PLEASE ALSO NOTE THIS LOCATION IS A "C" ZONE
 AND THE MEAN ROOF HEIGHT IS ABOVE 15'-0" PLEASE REVIEW
 MULTIPLIERS FOR EXPOSURE AND HEIGHT.
  
  
 FROM 1ST REVIEW! THE FL 10884 REPORT SUBMITTED FOR A
 SOLAR POWERED ROOF VENTILATION FAN DOES NOT INDICATE
 ANY WIND DESIGN CRITERIA BUT REFERS TO A MIAMI-DADE
 TEST REPORT 51567.01-122-18 THAT WAS COMPLETED UNDER
 THE 2001 VERSION OF THE FLORIDA BUILDING CODE AND TEST
 WAS FOR PRESSURES OF 110 MPH FASTEST MILE. THE 2004 &
 2007 FBC USE A 3 SECOND GUST CONVERSION CHARTS WOULD
 MAKE THE 110 FASTEST MILE, 130 MPH 3 SECOND GUST.THE
 CITY OF WEST PALM BEACH IS LOCATED WITHIN A 140 MPH
 WIND ZONE. THIS PRODUCT WILL NEED TO BE RE-EVALUATED TO
 THE 140 MPH WIND ZONE, AND FIGURE IN THE HEIGHT AND
 EXPOSURE ADJUTMENT FACTORS.
 R301.1.2.1 WIND LIMITATIONS.
 R301.2.1.1 WIND DESIGN CRITERIA
 R301.1.2.1.3 WIND SPEED CONVERSION
 R301.2.1.4 EXPOSURE CATEGORY
 R301.2.1.5 BASIC WIND SPEED
  
 SECOND REVIEW THE SAME ITEMS OUTSTANDING.
 2) SDI SOLAR HEATER PANEL:
 2.1) PLEASE PROVIDE THE ACTUAL PANEL SIZE IN SQ FT
 2.2 PLEASE PROVIDE THE ACTUAL MEAN ROOF HEIGHT IN FT.
 2.3 PLEASE PROVIDE THE ACTUAL ROOF PITCH AND CIRCLE
 WHICH INSTALATION METHOD TO BE USED.
  
 IN A WORSE CASE SCENERIO;
 20 SQ FT AREA / LOCATED IN A ZONE TWO
 EXPOSURE "C"
 ROOF MEAN ROOF HEIGHT OF 35'
  
 -51.7X1.45= -74.96 PSF
  
 3/8" LAG SCREWS (FASTENER) @ 48 SQ FT
 74.96X 48 SQ FT= 3598/4= 899.52LBS PULL OUT PER
 FASTENER
 PLEASE PROVIDE DOCUMENTATION ON THE FASTENER FOR THE
 PULL OUT STRENGTH
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved