| 2010-11-30 10:15:59 | BUILDING PLAN REVIEW |
| | PERMIT: 10070762 |
| | ADD: 8000 VIA VILLAGIO |
| | CONT: SDI SOLAR INC |
| | TEL: (561)722-3088 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE SOLAR ROOF POWERED ROOF VENTILATION FAN DOES NOT |
| | HAVE A CURRENT FLORIDA APPROVAL UNDER THE 2007 FBC. THE |
| | SUBMITTAL THAT IS REFRENECING THE 14 INCH SOLAR STAR |
| | VENT AND LETTER OF EQIVALENCY WILL REQUIRE EITHER |
| | APPLICATION TO THE STATE UNDER RULE 9B-72 (1)(D) OR |
| | SUBMITTAL TO THE CITY FOR A LOCAL APPROVAL. THE CITY OF |
| | WEST PALM BEACH REQUIRES THE SAME TEN CRITERIA AS THE |
| | STATE FOR A LOCAL APPROVAL, TO BE SUBMITTED TO ASSITANT |
| | BUILDING OFFICIAL ROBERT BROWN TO BE REVIEWED. |
| | |
| | |
| | FROM 1ST REVIEW! THE FL 10884 REPORT SUBMITTED FOR A |
| | SOLAR POWERED ROOF VENTILATION FAN DOES NOT INDICATE |
| | ANY WIND DESIGN CRITERIA BUT REFERS TO A MIAMI-DADE |
| | TEST REPORT 51567.01-122-18 THAT WAS COMPLETED UNDER |
| | THE 2001 VERSION OF THE FLORIDA BUILDING CODE AND TEST |
| | WAS FOR PRESSURES OF 110 MPH FASTEST MILE. THE 2004 & |
| | 2007 FBC USE A 3 SECOND GUST CONVERSION CHARTS WOULD |
| | MAKE THE 110 FASTEST MILE, 130 MPH 3 SECOND GUST.THE |
| | CITY OF WEST PALM BEACH IS LOCATED WITHIN A 140 MPH |
| | WIND ZONE. THIS PRODUCT WILL NEED TO BE RE-EVALUATED TO |
| | THE 140 MPH WIND ZONE, AND FIGURE IN THE HEIGHT AND |
| | EXPOSURE ADJUTMENT FACTORS. |
| | R301.1.2.1 WIND LIMITATIONS. |
| | R301.2.1.1 WIND DESIGN CRITERIA |
| | R301.1.2.1.3 WIND SPEED CONVERSION |
| | R301.2.1.4 EXPOSURE CATEGORY |
| | R301.2.1.5 BASIC WIND SPEED |
| | |
| | SECOND REVIEW THE SAME ITEMS OUTSTANDING. |
| | 2) SDI SOLAR HEATER PANEL: |
| | 2.1) PLEASE PROVIDE THE ACTUAL PANEL SIZE IN SQ FT |
| | 2.2 PLEASE PROVIDE THE ACTUAL MEAN ROOF HEIGHT IN FT. |
| | 2.3 PLEASE PROVIDE THE ACTUAL ROOF PITCH AND CIRCLE |
| | WHICH INSTALATION METHOD TO BE USED. |
| | |
| | IN A WORSE CASE SCENERIO; |
| | 20 SQ FT AREA / LOCATED IN A ZONE TWO |
| | EXPOSURE "C" |
| | ROOF MEAN ROOF HEIGHT OF 35' |
| | |
| | -51.7X1.45= -74.96 PSF |
| | |
| | 3/8" LAG SCREWS (FASTENER) @ 48 SQ FT |
| | 74.96X 48 SQ FT= 3598/4= 899.52LBS PULL OUT PER |
| | FASTENER |
| | PLEASE PROVIDE DOCUMENTATION ON THE FASTENER FOR THE |
| | PULL OUT STRENGTH |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |