| 2010-07-29 13:34:10 | *****DENIED***** |
| | |
| | NOTE: SCOPE OF WORK HAS INCREASED FROM ORIGINAL EXPIRED |
| | PERMIT #06082252. ORIGINAL DESIGN APPEARS TO BE VALID |
| | FOR ONLY SUITE #6 AND SUITE #7. INCREASED VALUE MAY NOT |
| | BE ACCURATE. INCREASED SCOPE MAY REQUIRE NEW SIGN/SEAL. |
| | |
| | SHEET A-3 |
| | 1) MERCANTILE OCCUPANCIES REQUIRE 2-HOUR SEPARATION |
| | FROM STORAGE OCCUPANCIES (REFERENCE NFPA 101, TABLE |
| | 6.1.14.4.1B). |
| | |
| | 2) MERCANTILE OCCUPANCIES (SUITE # 7) REQUIRE TWO EXITS |
| | WHEN THE TRAVEL DISTANCE TO AN EXIT EXCEEDS 75 FEET |
| | (REFERENCE NFPA 101, SECTION 37.2.4.3). |
| | |
| | 3) STORAGE OCCUPANCIES REQUIRE TWO EXITS WHEN THE |
| | TRAVEL DISTANCE TO AN EXIT EXCEEDS 50 FEET (REFERENCE |
| | NFPA 101, SECTION 42.2.4.1(2) AND TABLE 42.2.5). |
| | |
| | 4) PROVIDE ADDRESS SUITE NUMBERS AT LEAST SIX-INCHES IN |
| | HEIGHT AND PLACED IN A VISIBLE LOCATION FROM THE ROAD |
| | (REFERENCE NFPA 1, SECTION 10.12.1.2). |
| | |
| | 5) PROVIDE PORTABLE FIRE EXTINGUISHERS PER NFPA 10. |
| | |
| | 6) FIRE RATED WALLS, PARTITIONS ETC. SHALL BE |
| | IDENTIFIED WITH SIGNS OR STENCILING READING "FIRE |
| | BARRIER-PROTECT ALL OPENINGS" OR SIMILAR LANGUAGE. |
| | LETTERING SHALL BE IN 4-INCHES HIGH, 1/2-INCH STROKE, |
| | AND SPACED NOT MORE THAN 15-FEET ON-CENTER (REFERENCE |
| | NFPA 101, SECTION 8.3.2.4). |
| | |
| | 7) PROVIDE MECHANICAL DUCT DAMPER LOCATIONS IF |
| | APPLICABLE. |
| | |
| | SHEET E-1 |
| | 1) PROVIDE EMERGENCY LIGHTING FOR WEST AREA OF SUITE |
| | #2. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |