Plan Review Notes
Plan Review Notes For Permit 10070718
Permit Number 10070718
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-07-29 13:34:10*****DENIED*****
  
 NOTE: SCOPE OF WORK HAS INCREASED FROM ORIGINAL EXPIRED
 PERMIT #06082252. ORIGINAL DESIGN APPEARS TO BE VALID
 FOR ONLY SUITE #6 AND SUITE #7. INCREASED VALUE MAY NOT
 BE ACCURATE. INCREASED SCOPE MAY REQUIRE NEW SIGN/SEAL.
  
 SHEET A-3
 1) MERCANTILE OCCUPANCIES REQUIRE 2-HOUR SEPARATION
 FROM STORAGE OCCUPANCIES (REFERENCE NFPA 101, TABLE
 6.1.14.4.1B).
  
 2) MERCANTILE OCCUPANCIES (SUITE # 7) REQUIRE TWO EXITS
 WHEN THE TRAVEL DISTANCE TO AN EXIT EXCEEDS 75 FEET
 (REFERENCE NFPA 101, SECTION 37.2.4.3).
  
 3) STORAGE OCCUPANCIES REQUIRE TWO EXITS WHEN THE
 TRAVEL DISTANCE TO AN EXIT EXCEEDS 50 FEET (REFERENCE
 NFPA 101, SECTION 42.2.4.1(2) AND TABLE 42.2.5).
  
 4) PROVIDE ADDRESS SUITE NUMBERS AT LEAST SIX-INCHES IN
 HEIGHT AND PLACED IN A VISIBLE LOCATION FROM THE ROAD
 (REFERENCE NFPA 1, SECTION 10.12.1.2).
  
 5) PROVIDE PORTABLE FIRE EXTINGUISHERS PER NFPA 10.
  
 6) FIRE RATED WALLS, PARTITIONS ETC. SHALL BE
 IDENTIFIED WITH SIGNS OR STENCILING READING "FIRE
 BARRIER-PROTECT ALL OPENINGS" OR SIMILAR LANGUAGE.
 LETTERING SHALL BE IN 4-INCHES HIGH, 1/2-INCH STROKE,
 AND SPACED NOT MORE THAN 15-FEET ON-CENTER (REFERENCE
 NFPA 101, SECTION 8.3.2.4).
  
 7) PROVIDE MECHANICAL DUCT DAMPER LOCATIONS IF
 APPLICABLE.
  
 SHEET E-1
 1) PROVIDE EMERGENCY LIGHTING FOR WEST AREA OF SUITE
 #2.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
  
  