| Plan Review Notes For Permit 10070707 |
| Permit Number |
10070707 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-29 15:00:15 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE PAGE 11 OF THE PRODUCT APPROVAL, CONNECTION TYPE | | | 3 IS HIGHLIGHTED BUT THIS CONNECTION TYPE IS NOT | | | PERMITTED IN MASONRY SUBSTRATE. | | | | | | 2. PLEASE REVISE INSTALLATION SCHEDULE TO SPECIFY | | | SHUTTER CONNECTION MOUNTING TYPE, WHICH SHOULD | | | CORRELATE WITH THE ANCHOR CHARTS (FOR INSTANCE, 3 TOP). | | | | | | 3. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | | INSTALLATION SCHEDULE,. FBC R301, FBC1609, FBC*106. | | | | | | 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. | | | APPLICATION STATES IT IS THROUGH THE GARAGE, OVERHEAD | | | GARAGE DOOR CANNOT BE THE EMERGENCY ESCAPE. PLEASE SHOW | | | ENOUGH INFORMATION ON THE PLAN TO SHOW COMPLIANCE WITH | | | FBCR310.4. | | | | | | |
|