| Date |
Text |
| 2010-07-28 09:52:14 | BUILDING REVISION APPROVED WITH PROVISO: |
| | |
| | 1- REVISE DESIGN PRESSURES ON SHEET S-1. DESIGN |
| | PRESSURES SHOWN ON THE 2 STORY SKETCH DON'T MATCH THE |
| | DESIGN PRESSURES SHOWN UNDER THE TWO STORY WORST CASE |
| | SCENARIO AND UNDER THE WIND PRESSURES SHOWN FOR THE TWO |
| | STORY EDGE AND INTERIOR ZONES. SEE COMMENTS ON SHEET |
| | S-1 SUBMITTED. |
| | |
| | 2- PROVIDE COMPLETE STRUCTURAL DRAWINGS SHOWING |
| | HOISTWAY CONSTRUCTION TO SUPPORT THE ELEVATOR GUIDE |
| | RAILS. SEE ELEVATOR SPECIFICATIONS SUBMITTED ON |
| | 7/29/10. |
| | |
| | |
| | |
| | ***REMAINDER*** |
| | |
| | PROVIDE INFORMATION REQUESTED ON PROVISO DATED 7/01/10. |
| | SEE COPY BELOW. |
| | |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF TILE ADHESIVE. TITESET ROOFING ADHESIVE |
| | SUBMITTED IS NOT LISTED ON THE ROOF TILE NOA. NEED TO |
| | SHOW WHAT'S THE MIN. ATTACHMENT RESISTANCE TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| | |
| | B) SEALOFLEX WATERPROOFING NOA 05-0901.04: ENGINEER |
| | NEEDS TO REVISE THE RAS 117 CALCULATIONS. THE MIN. |
| | FASTENER SEPARATION SHALL NOT BE LESS THAN 4"O.C. SEE |
| | SEC. 8.1 OF RAS 117. |
| | |
| | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 105.3.3 CITY AMENDMENTS TO |
| | FBC. THIS APPLIES TO PRODUCT APPROVALS THAT NEED TO BE |
| | RE-SUBMITTED. |
| | |
| | 3- SHEET S1: REVISE DESIGN PRESSURES FOR WALL OPENINGS |
| | IN EXPOSURE "C". REVISE SKETCH FOR ONE STORY ALSO AND |
| | COORDINATE WITH DESIGN PRESSURES SHOWN AT BOTTOM OF |
| | PAGE. |