2010-08-04 09:36:03FUEL GAS PLAN REVIEW #1
 DENIED:
  
 1.PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS
 ALL CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 9.
 RISER DIAGRAM/SHUTOFFS
  
 2. BTU LOAD AND PIPE SIZE FOR WATER HEATER IS NOT SHOWN
 ON PLAN.
  