2010-07-29 17:16:47*****REVIEW COMMENTS - FIRE*****
  
 1) SHEET A-2: RESTROOM DOOR SWING OBSTRUCTS ACCESS TO
 REAR EXIT (NFPA 101, SECTION 7.2.1.4.4).
  
 2) SHEET A-2: EQUIPMENT #60 (HOOD SUPPRESSION SYSTEM)
 NOT FOUND ON FLOOR PLAN. SEPARATE PLANS AND PERMIT
 REQUIRED FOR SUPPRESSION SYSTEM.
  
 3) TYPE K PORTABLE FIRE EXTINGUISHER PROVIDED FOR
 KITCHEN AREA; PROVIDE 2A-10BC EXTINGUISHER FOR
 NON-KITCHEN SPACE.
  
 4) SHEET A-4: PROVIDE BUILDING ADDRESS NUMBERS AT LEAST
 SIX-INCHES IN HEIGHT ON BUILDING SO NUMERALS ARE
 VISIBLE FROM THE ROAD FRONTING THE PROPERTY (NFPA 1,
 SECTION 10.12.1).
  