| Plan Review Notes For Permit 10070629 |
| Permit Number |
10070629 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-29 17:16:47 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) SHEET A-2: RESTROOM DOOR SWING OBSTRUCTS ACCESS TO | | | REAR EXIT (NFPA 101, SECTION 7.2.1.4.4). | | | | | | 2) SHEET A-2: EQUIPMENT #60 (HOOD SUPPRESSION SYSTEM) | | | NOT FOUND ON FLOOR PLAN. SEPARATE PLANS AND PERMIT | | | REQUIRED FOR SUPPRESSION SYSTEM. | | | | | | 3) TYPE K PORTABLE FIRE EXTINGUISHER PROVIDED FOR | | | KITCHEN AREA; PROVIDE 2A-10BC EXTINGUISHER FOR | | | NON-KITCHEN SPACE. | | | | | | 4) SHEET A-4: PROVIDE BUILDING ADDRESS NUMBERS AT LEAST | | | SIX-INCHES IN HEIGHT ON BUILDING SO NUMERALS ARE | | | VISIBLE FROM THE ROAD FRONTING THE PROPERTY (NFPA 1, | | | SECTION 10.12.1). | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 |
|