Plan Review Notes
Plan Review Notes For Permit 10070629
Permit Number 10070629
Review Stop E
Sequence Number 1
Notes
Date Text
2010-08-17 08:22:331) NO ENERGY CALCULATION 13-415.B.1 , AND SPACE CONTROL
 PER 13-415.AB.1.2
  
 2) SERVICE GROUNDING NOT PER CODE
  
 3) EQUIPMENT GROUND FOR FEEDER NOT PER CODE
  
 4) SEE 210.8 B 2 FOR GFCI REQUIREMENTS
  
 5) CONFIRM AIC RATING BEFORE FIRST INSPECTION.