| 2010-08-17 08:22:33 | 1) NO ENERGY CALCULATION 13-415.B.1 , AND SPACE CONTROL | | | PER 13-415.AB.1.2 | | | | | | 2) SERVICE GROUNDING NOT PER CODE | | | | | | 3) EQUIPMENT GROUND FOR FEEDER NOT PER CODE | | | | | | 4) SEE 210.8 B 2 FOR GFCI REQUIREMENTS | | | | | | 5) CONFIRM AIC RATING BEFORE FIRST INSPECTION. |
|