| Plan Review Notes For Permit 10070561 |
| Permit Number |
10070561 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-03 11:15:58 | MECHANICAL PLAN REVIEW | | | PERMIT: 10070561 | | | ADD: 716 NEY YORK ST | | | CONT: TO BE DETERMINED | | | CONTACT: PENE LATHAM | | | TEL: (561)832-1500 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE- MECHANICAL | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS. | | | N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL | | | BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION | | | AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD | | | A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO | | | COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE | | | MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE | | | BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2. | | | N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN | | | APPLICABLE (SEE SECTION N1100.7.3), MEET THE | | | PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR | | | INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND | | | EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING | | | RETROFITTED OR REPLACED. | | | | | | 2) SHEET 6.1 MECHANICAL SHEET IS MISSING THE A/C SYSTEM | | | DESIGN DATA, BLANK! | | | | | | | | | JAMES A. WITMER C.B.O. | | | SFP-100 | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: (561)805-6715 | | | FAX:(561)805-6731 | | | E-MAIL: [email protected] | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|