| 2010-08-16 11:00:32 | PLUMBING PLAN REVIEW |
| | PERMIT: 10070561 |
| | ADD: 716 NEY YORK ST |
| | CONT: TO BE DETERMINED |
| | CONTACT: PENE LATHAM |
| | TEL: (561)832-1500 |
| | |
| | FL BLD CODE PLUMBING= 2007 FLORIDA BUILDING CODE- |
| | PLUMBING |
| | W/ 2009 FBC SUPPLEMENTS * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET 6.1 ISOMETRIC PLAN THE NEW BATHROOM INDICATES |
| | A WATERCLOSET AND SHOWER CONNECTED TO THE SAME STACK. |
| | PLEASE REVIEW P3107.3 CONNECTIONS AT DIFFERENT LEVEL. |
| | THE UPPER FIXTURE SHALL NOT BE A WATER CLOSET. |
| | CURRENTLY SHOWN THE SHOWER IS NOT VENTED. |
| | |
| | 2) THE KITCHEN THE PLANS INDICATE WINDOWS REQUIRING THE |
| | VENT TO BE ROUTED PAST THE FRAMED WINDOW OPENING. |
| | R602.2.7 DRILLING AND NOTCHING???STUDS. DRILLING AND |
| | NOTCHING OF STUDS SHALL BE IN ACCORDANCE WITH THE |
| | FOLLOWING: |
| | |
| | 1.NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING |
| | PARTITION MAY BE CUT OR NOTCHED TO A DEPTH NOT |
| | EXCEEDING 25 PERCENT OF ITS WIDTH. STUDS IN NONBEARING |
| | PARTITIONS MAY BE NOTCHED |
| | TO A DEPTH NOT TO EXCEED 40 PERCENT OF A SINGLE STUD |
| | WIDTH. |
| | |
| | 2. DRILLING. ANY STUD MAY BE BORED OR DRILLED, PROVIDED |
| | THAT THE DIAMETER OF THE RESULTING HOLE IS NO MORE THAN |
| | 60 PERCENT OF THE STUD WIDTH, THE EDGE OF THE HOLE IS |
| | NO MORE THAN 5/8 |
| | INCH (16 MM) TO THE EDGE OF THE STUD, AND THE HOLE IS |
| | NOT LOCATED IN THE SAME SECTION AS A CUT OR NOTCH. |
| | STUDS LOCATED IN EXTERIOR WALLS OR BEARING PARTITIONS |
| | DRILLED OVER 40 PERCENT |
| | AND UP TO 60 PERCENT SHALL ALSO BE DOUBLED WITH NO MORE |
| | THAN TWO SUCCESSIVE DOUBLED STUDS BORED. SEE FIGURES |
| | R602.2.7(1) AND R602.2.7(2). |
| | |
| | PLEASE NOTE AN AIR ADMITTANCE DEVICE MAY BE USED |
| | INSTEAD OF THE 2 INCH VENT. |
| | |
| | 3) WITHIN THE NEW HALF BATH THE SANITARY VENT WILL |
| | EITHER CUT OR NOTCH THE TOP AND BOTTOM PLATE PLEASE |
| | REVIEW SECTION: R602.2.7.1 DRILLING AND NOTCHING OF TOP |
| | PLATE. WHEN PIPING OR DUCTWORK IS PLACED IN OR PARTLY |
| | IN AN EXTERIOR WALL OR INTERIOR LOAD-BEARING WALL, |
| | NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP |
| | PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A |
| | GALVANIZED METAL TIE OF NOT LESS THAN 0.054 INCHES |
| | THICK (1.37 MM) (16 GA) AND 11/2 INCHES (38 MM) WIDE |
| | SHALL BE FASTENED ACROSS AND TO THE PLATE AT EACH SIDE |
| | OF THE OPENING WITH NOT LESS THAN EIGHT 10D (0.148 INCH |
| | DIAMETER) NAILS HAVING A MINIMUM LENGTH OF 11/2 INCHES |
| | (38 MM) AT EACH SIDE OR EQUIVALENT. SEE FIGURE |
| | R602.2.7(1). |
| | EXCEPTION: WHEN THE ENTIRE SIDE OF THE WALL WITH THE |
| | NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL |
| | SHEATHING. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |