| Date |
Text |
| 2010-08-12 11:37:25 | GAS PLAN REVIEW |
| | PERMIT: 10070561 |
| | ADD: 716 NEY YORK ST |
| | CONT: TO BE DETERMINED |
| | CONTACT: PENE LATHAM |
| | TEL: (561)832-1500 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE- GAS |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1) PLEASE PROVIDE THE DEVELOPED LENGTH OF THE GAS |
| | PIPING FROM THE METER TO THE LAST APPLIANCE, BTU OF |
| | EACH APPLIANCE. |
| | |
| | 1A) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. |
| | SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER), |
| | TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER FBC-2007 FUEL |
| | GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 1B) 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, |
| | ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL TUBING FOR EACH |
| | PIPE SIZE IF BEING USED. |
| | |
| | 1C) NEW GAS INSTA-HOT WATER HEATER PLEASE PROVIDE |
| | MANUFACTURERS SPEC FOR BTU, AND APPROVAL FOR EXTERIOR |
| | LOCATIONS. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2007 FUEL GAS CODE SEC 402.2 & |
| | RESIDENTIAL CODE SEC. G2413.2. |
| | |
| | 1D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 THRU 402.6.1 AND |
| | TABLES 402.4(1) THRU |
| | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). |
| | |
| | 1E) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2004 |
| | FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY .5 PSI OR |
| | 2 PSI. |
| | |
| | |
| | |