| Date |
Text |
| 2010-08-12 11:00:07 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 10070561 |
| | ADD: 716 NEY YORK ST |
| | CONT: TO BE DETERMINED |
| | CONTACT: PENE LATHAM |
| | TEL: (561)832-1500 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE SHEET 1.1 INDICATES A TWO STORY TO BE REMODELED |
| | THERE ARE NO OTHER REFERENCES IN EITHER THIS PLAN NOR |
| | PERMIT APPLICATION AND WILL NOT BE PART OF WORK TO BE |
| | COMPLETED UNDER THIS PERMIT . |
| | |
| | 1) EITHER A CONTRACTOR OR OWNER/ BUILDER WILL BE |
| | REQUIRED TO SIGN ON TO THE PERMIT APPLICATION. |
| | |
| | 2) NOTE, ONLY ONE SET OF PLANS WERE SUBMITTED TO REVIEW |
| | FOR CODE COMPLIANCE. BEFORE A PERMIT WILL BE ISSUED TWO |
| | SETS OF PLANS AND ASSOCIATED DOCUMENTS WILL NEED TO BE |
| | SUPPLIED FOR REVIEW AND APPROVAL STAMPING. ONE FOR THE |
| | FIELD INSPECTORS AND ONE FOR RECORD RETENTION. 106.3.1/ |
| | 2007 FBC-B ADMINISTRATIVE CODE. |
| | |
| | 3) PLEASE PROVIDE ON THE PLANS WHO IS THE DESIGNER OF |
| | RECORD, SINCE THIS IS A SINGLE FAMILY RESIDENCE IT DOES |
| | NOT NEED TO BE A ARCHITECT OR ENGINEER WHO ARE COVERED |
| | UNDER FL S 481 AND 471. FBC-B 106.1* DESIGNERS NAME AND |
| | CONTACT NUMBER TO BE ABLE TO CONTACT THE DESIGNER IN |
| | CASE OF QUESTIONS. |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 5A) WINDOWS RULE 9B-72(31) (B) |
| | SINGLE HUNG |
| | CASEMENT |
| | 5B) EXTERIOR DOORS RULE 9B-72(31) (A) |
| | 5C) ROOF ASSEMBLIES RULE 9B-72(31) (D) |
| | |
| | PLEASE NOTE IF THE CONTRACTOR DOES NOT SUPPLY THE |
| | PRODUCT APPROVALS BEFORE TIME OF ISSUANCE, THESE ITEMS |
| | CAN BE A BUILDING PROVISO: WHICH MEANS THE PRODUCT |
| | APPROVALS CAN BE BROUGHT IN AFTER ISSUANCE BUT WILL BE |
| | CONSIDERED A REVISION WITH FURTHER REVIEW AND |
| | ASSOCIATED FEES. THE DESIGN PRESSURES INDICATED ON |
| | SHEET 5.1 ARE CORRECT. |
| | |
| | 6) SHEET 3.1 IN THE DESIGN PARAMETERS AND CODE |
| | REFERENCES, BOTH MAKE REFERENCES TO THE 2004 FBC, |
| | PLEASE REVISE TO THE 2007 FBC WITH 2009 SUPPLEMENTS. |
| | PLEASE ALSO INCLUDE UNDER THE 2007 EXISTING BUILDING |
| | CODE COMPLIANCE WITH SECTION 401.4 A DESIGN |
| | PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A |
| | COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | |
| | 7) THE FLOOR PLAN SHEET 3.1 INDICATES A NEWLY REMODELED |
| | RESTROOM WITH THE SHOWER NEXT TO A SINGLE HUNG WINDOW |
| | PLEASE REVIEW R308.4(9) HAZARDOUS LOCATIONS. |
| | |
| | 8) THE PLANS INDICATE IN SECTION 3/6.1 A TYPICAL GABLE |
| | WALL PLEASE REVIEW R602.1.2(1.1) FOR REQUIRED FIRE |
| | BLOCKING SEPARATING VERTICALLY AT THE CEILING. |
| | |
| | 9) RESIDENTIAL: ENERGY CODE 2007 SUPPLEMENTS. |
| | N1100.0.3 ADDITIONS. ADDITIONS TO EXISTING RESIDENTIAL |
| | BUILDINGS SHALL BE CONSIDERED NEW BUILDING CONSTRUCTION |
| | AND SHALL COMPLY WITH THE REQUIREMENTS OF EITHER METHOD |
| | A OR B AS APPLICABLE. ADDITIONS THAT ARE UNABLE TO |
| | COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE |
| | MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE |
| | BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2. |
| | N1100.0.4 RENOVATIONS. RENOVATED BUILDINGS SHALL, WHEN |
| | APPLICABLE (SEE SECTION N1100.7.3), MEET THE |
| | PRESCRIPTIVE REQUIREMENTS CONTAINED IN METHOD B FOR |
| | INSULATION, HVAC SYSTEMS, WATER HEATING SYSTEMS AND |
| | EXTERIOR ENVELOPE FOR THOSE COMPONENTS BEING |
| | RETROFITTED OR REPLACED. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |