2010-08-19 16:00:072007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) FBCR M1602.2 PROHIBITS RETURN AIR FROM A BATHROOM.
 THE PLANS INDICATE RETURNS AT BOTH BATHROOMS. SUBMIT
 CORRECTED PLANS.
  
 2) THE PLANS INDICATE THAT ALL OF THE DUCT WORK IS 8"
 FLEX AND THAT ALL OF THE ROOMS WILL BE SUPPLIED WITH
 300 CFM OF AIR. THIS DOES NOT COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE FOR CORRECTLY
 SIZING AN HVAC SYSTEM. FBCR M1601.1 REQUIRES DUCT
 SYSTEMS TO BE DESIGNED IN ACCORDANCE WITH ACCA MANUAL D
 OR OTHER APPROVED METHOD. THE HEAT GAIN AND BTU/HR OF
 COOLING REQUIRED FOR EACH ROOM NEEDS TO BE DETERMINED.
 THEN THE DUCT CAN BE PROPERLY SIZED TO THE CFM AND
 VELOCITY NEEDED FOR THE ROOM SERVED IN ACCORDANCE WITH
 THE MANUAL J AND MANUAL D DUCT DESIGN. SUBMIT CORRECTED
 PLANS.
  
 3) THE NAME AND LICENSE NUMBER OF THE HVAC CONTRACTOR
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
  