| Plan Review Notes For Permit 10070545 |
| Permit Number |
10070545 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-08-19 16:00:07 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) FBCR M1602.2 PROHIBITS RETURN AIR FROM A BATHROOM. | | | THE PLANS INDICATE RETURNS AT BOTH BATHROOMS. SUBMIT | | | CORRECTED PLANS. | | | | | | 2) THE PLANS INDICATE THAT ALL OF THE DUCT WORK IS 8" | | | FLEX AND THAT ALL OF THE ROOMS WILL BE SUPPLIED WITH | | | 300 CFM OF AIR. THIS DOES NOT COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE FOR CORRECTLY | | | SIZING AN HVAC SYSTEM. FBCR M1601.1 REQUIRES DUCT | | | SYSTEMS TO BE DESIGNED IN ACCORDANCE WITH ACCA MANUAL D | | | OR OTHER APPROVED METHOD. THE HEAT GAIN AND BTU/HR OF | | | COOLING REQUIRED FOR EACH ROOM NEEDS TO BE DETERMINED. | | | THEN THE DUCT CAN BE PROPERLY SIZED TO THE CFM AND | | | VELOCITY NEEDED FOR THE ROOM SERVED IN ACCORDANCE WITH | | | THE MANUAL J AND MANUAL D DUCT DESIGN. SUBMIT CORRECTED | | | PLANS. | | | | | | 3) THE NAME AND LICENSE NUMBER OF THE HVAC CONTRACTOR | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|