| Plan Review Notes For Permit 10070545 |
| Permit Number |
10070545 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-26 16:41:45 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBC M1401.3. | | | | | | 2) SUBMIT TWO SETS OF FLOOR PLANS SHOWING THE LOCATIONS | | | OF THE AIR HANDLERS, CONDENSERS, DISCONNECTS, SERVICE | | | OUTLETS, DUCT SIZES, SUPPLY LOCATIONS, GRILL SIZES, CFM | | | AT EACH SUPPLY, RETURN LOCATIONS AND SIZES, TRANSFER | | | DUCT/GRILL LOCATIONS AND SIZES. SPECIFY THE HEATING AND | | | COOLING EQUIPMENT ON THE PLANS INCLUDING MODEL NUMBERS | | | AND SPECIFICATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|