2010-07-26 16:41:452007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBC M1401.3.
  
 2) SUBMIT TWO SETS OF FLOOR PLANS SHOWING THE LOCATIONS
 OF THE AIR HANDLERS, CONDENSERS, DISCONNECTS, SERVICE
 OUTLETS, DUCT SIZES, SUPPLY LOCATIONS, GRILL SIZES, CFM
 AT EACH SUPPLY, RETURN LOCATIONS AND SIZES, TRANSFER
 DUCT/GRILL LOCATIONS AND SIZES. SPECIFY THE HEATING AND
 COOLING EQUIPMENT ON THE PLANS INCLUDING MODEL NUMBERS
 AND SPECIFICATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]