2010-07-26 13:46:48BUILDING PLAN REVIEW
 PERMIT: 10060179/
 REVISION: 10070511
 ADD: 512 SPENCER DR
 CONT: M. J. SIMPSON CORP.
 TEL: (954)275-5205
  
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISOS:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET AD-1.01 NOTE NUMBERS 4 & 5 & SHEET A-1.01,
 DOOR # 104-6 & 104-7 AND A-6.01 INDICATE THE REMOVAL
 AND REPLACEMENT OF DOORS. THE DOOR SCHEDULE INDICATE NO
 FIRE RATING. THIS WALL APPEARS TO BE A 4 HR FIRE WALL
 REQUIRING THESE DOORS TO HAVE 3 HOUR OPENING
 PROTECTIVES. 2007 FBC-B TABLE 715.4.
  
 2) SHEET AD-1.01 NOTES 3 & 16 INDICATE THE REMOVAL OF
 STOREFRONT WINDOWS AND DOORS, SHEET A-1.01 INDICATE NEW
 STOREFRONT DOORS, THE S-1 SHEET PROVIDES THE ASSOCIATED
 POSITIVE & NEGATIVE PRESSURES, THE CONTRACTOR WILL NEED
 TO SUPPLY PRODUCT APPROVALS FOR THESE NEW COMPONENTS
 AND CLADDING.
  
 2A) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A ) STOREFRONT EXTERIOR GLAZED DOORS.
 3B) 7/26/2010 COMPLIED STOREFRONT WINDOW SYSTEM- ARCH
 NOA 09-1110.03
 3C) 3 HOUR FIRER RATED DOORS
  
 2B) SEMI- COMPLIED STOREFRONT WINDOWS ARCH NOA
 09-1110.03. 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) SHEET A-1.01 NEW ACCESSIBLE RAMP INDICATES THE
 BOTTOM LANDING TO BE A DISTANCE OF 4'-8" LONG, PLEASE
 REFER TO 11-4.8.4(2) THE BOTTOM OF EACH RAMP SHALL HAVE
 NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 4) SHEET A-1.01 NOTE 28 INDICATES THE INSTALLATION OF
 NEW LANDING AND STAIRS. A-1.02 DETAILS 4 & 5 INDICATE A
 SECTION THROUGH THE STAIR BUT NO REFERENCE TO THE
 REQUIRED HANDRAILS FBC-B 1009.10 , 1012 & 11-4.1.3.8(D)
 .
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved