Plan Review Notes
Plan Review Notes For Permit 10070389
Permit Number 10070389
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2010-09-29 12:43:582223 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10070389
  
  
 1. SHEETS A-1 AND A-2 DO NOT MATCH. SHEET A-2 DISPLAYS
 A LARGER PORTION OF THE BUILDING THAN THAT DESCRIBED ON
 SHEET A-1.
  
 2. THE LIFE SAFETY PLAN ON SHEET A-3 DOES NOT MATCH THE
 PROPOSED FLOOR PLAN SHOWN ON PAGE A-4. SEVERAL DOORS
 ARE MISSING FROM THE LIFE SAFETY PLAN.
  
 3. IT APPEARS THAT 500 OCCUPANTS ARE PLANNED BUT NO
 INFORMATION PROVIDED REGARDING A FIRE ALARM SYSTEM
 CAPABLE OF PROVIDING VOICE EVACUATION CAPABILITIES.
 PLEASE PROVIDE THESE DETAILS.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM INSTALLATION AND FIRE SPRINKLER REMODELING.
  
 5. THE PLANS ARE VERY CONFUSING AND THE SEVERAL SHEETS
 DO NOT APPEAR TO CORRESPOND WITH ONE ANOTHER. PLEASE
 COORDINATE SHEETS
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION