| Plan Review Notes For Permit 10070389 |
| Permit Number |
10070389 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2010-09-29 12:43:58 | 2223 PALM BEACH LAKES BOULEVARD | | | PERMIT NUMBER 10070389 | | | | | | | | | 1. SHEETS A-1 AND A-2 DO NOT MATCH. SHEET A-2 DISPLAYS | | | A LARGER PORTION OF THE BUILDING THAN THAT DESCRIBED ON | | | SHEET A-1. | | | | | | 2. THE LIFE SAFETY PLAN ON SHEET A-3 DOES NOT MATCH THE | | | PROPOSED FLOOR PLAN SHOWN ON PAGE A-4. SEVERAL DOORS | | | ARE MISSING FROM THE LIFE SAFETY PLAN. | | | | | | 3. IT APPEARS THAT 500 OCCUPANTS ARE PLANNED BUT NO | | | INFORMATION PROVIDED REGARDING A FIRE ALARM SYSTEM | | | CAPABLE OF PROVIDING VOICE EVACUATION CAPABILITIES. | | | PLEASE PROVIDE THESE DETAILS. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM INSTALLATION AND FIRE SPRINKLER REMODELING. | | | | | | 5. THE PLANS ARE VERY CONFUSING AND THE SEVERAL SHEETS | | | DO NOT APPEAR TO CORRESPOND WITH ONE ANOTHER. PLEASE | | | COORDINATE SHEETS | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|