| 2010-08-26 11:23:40 | FBC PLUNBING 2007 REVIEW #2 | | | DENIED: | | | | | | 1. WITH THE ADDITION OF WATER CLOSETS IN THE WOMENS | | | ROOM, ONE STALL WOULD NEED TO COMPLY WITH 11-4.22.4 | | | NOTE** THE REQUIRED FIXTURE COUNT FOR MEN IS 4 WC'S OR | | | 50% OF WC'S COULD BE URINALS. THE FIXTURE COUNT FOR | | | WOMEN WOULD BE 6 WC'S DUE TO POTTY PARITY. THE UNISEX | | | RESTROOM IS PERMITTED TO BE USED FOR THE WOMENS FIXTURE | | | COUNT | | | | | | 4. SHEET A-5 FBC 2007 11-4.17 ADA STALLS IN MENS AND | | | WOMENS ROOMS DO NOT COMPLY WITH FIGURE 30(E). | | | 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED, | | | THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL | | | COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE | | | STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING | | | WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES | | | (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING | | | DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D) | | | AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN | | | SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|