Plan Review Notes
Plan Review Notes For Permit 10070389
Permit Number 10070389
Review Stop P
Sequence Number 2
Notes
Date Text
2010-08-26 11:23:40FBC PLUNBING 2007 REVIEW #2
 DENIED:
  
 1. WITH THE ADDITION OF WATER CLOSETS IN THE WOMENS
 ROOM, ONE STALL WOULD NEED TO COMPLY WITH 11-4.22.4
 NOTE** THE REQUIRED FIXTURE COUNT FOR MEN IS 4 WC'S OR
 50% OF WC'S COULD BE URINALS. THE FIXTURE COUNT FOR
 WOMEN WOULD BE 6 WC'S DUE TO POTTY PARITY. THE UNISEX
 RESTROOM IS PERMITTED TO BE USED FOR THE WOMENS FIXTURE
 COUNT
  
 4. SHEET A-5 FBC 2007 11-4.17 ADA STALLS IN MENS AND
 WOMENS ROOMS DO NOT COMPLY WITH FIGURE 30(E).
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692