| Plan Review Notes For Permit 10070389 |
| Permit Number |
10070389 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-27 15:23:30 | FBC PLUNBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. IF FROM BUILDING TOTAL OCCUPANTS IS 614 THEN | | | REQUIRED WATER CLOSETS FOR WOMEN WOULD BE 5. | | | PLUMBING TABLE 403.1 | | | | | | 2. ONE SERVICE SINK WILL BE REQUIRED TABLE 403.1 | | | | | | 3. ONE UNISEX TOILET WOULD BE REQUIRED | | | E. IN ASSEMBLY AND MERCANTILE OCCUPANCIES, A UNISEX | | | TOILET ROOM, IN ACCORDANCE WITH SECTION 403.7, SHALL BE | | | PROVIDED WHERE AN AGGREGATE OF SIX OR MORE MALE AND | | | FEMALE WATER CLOSETS ARE REQUIRED. IN BUILDINGS OF | | | MIXED OCCUPANCY, ONLY THOSE WATER CLOSETS REQUIRED FOR | | | THE ASSEMBLY OR MERCANTILE OCCUPANCY SHALL BE USED TO | | | DETERMINE THE UNISEX TOILET ROOM REQUIREMENT. | | | | | | 4. FBC 2007 11-4.17 ADA STALL SHALL COMPLY WITH FIGURE | | | 30(E) | | | | | | 5. A DOMESTIC WATER RISER DIAGRAM IS REQUIRED. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | | | 6. ALTHOUGH THE FIXTURE COUNT MAY CHANGE, THE CURCUIT | | | VENT IN THE SANITARY RISER WILL REQUIRE A DRY VENT | | | BETWEEN THE LAST TWO WATER CLOSETS FBC PLUMBING 911.2 | | | | | | 7. 4" PIPE IS REQUIRED UP TO THE FIRST ADA WATER CLOSET | | | IN DRAWING. | | | PLUMBING TABLE 710.1 (2) | | | | | | 8. THE FLOOR DRAINS IN THE RESTROOMS REQUIRE TRAP | | | PRIMERS. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | |
|